The FC1008/12-xx is a compact 8 or 12 zone control unit. The control unit has been
designed to be very simple to use while offering exceptional flexibility via a comprehen-
sive feature list.
Detection
Each line programmable for current limited or non current limited operation
Detectors and call points on same line with functional differentiation (where allowed)
Intrinsically safe detectors via line coupler DC1192 and safety barrier SB3
Each line programmable for non-latch function and/or technical alarms
Inputs / Outputs
Dry contacts for general alarm and fault
2 or 6 monitored control lines 24 V/500 mA for horns, external remote transm., etc.
1 to 6 fire control relays, rated 10 A/250 V
Driver output per detector line
6 common driver control outputs
6 control inputs (1 programmable)
PMI
Individual indicator labeling with inscription stripe sets in various languages
Numeric display for alarm counter, clock, alarm delay count down, event memory
Individual isolate/test buttons for clear and easy user operation
Commissioning
Basic functions that can be adapted on-site if required without laptop
Simple “out of the box” start up with preset default values
Service function to poll date and time of last test alarm or last configuration change
Types Additional
line card
BS
Door
contact
RT Isolation
card
Fire control
relays
Key
switch
Special functions
FC1008-A - - (x) (6) (x) (standard function according to EN 54)
FC1008-B x - (x) (6) (x) according to British Standard
FC1008-C - - (x) (6) x with Nordic fire key switch (Nordic countries)
FC1008-D - - (x) (6) x PMI with fire brigade terminal (Swiss standard)
FC1008-E - - (x) (6) (x) with special EVAC control unit (Dutch standard)
FC1008-F - x - (6) (x) with interface for VdS peripherals (German standard)
FC1012-A - - (x) (6) (x) (standard function according to EN 54)
FC1012-B x - (x) (6) (x) according to British Standard
FC1012-C - - (x) (6) x with Nordic fire key switch (Nordic countries)
FC1012-F - x - (6) (x) with interface for VdS peripherals (German standard)
(x) = optional
Legend
Additional line card
BS
To provide line continuity with diode bases
according to British Standard
Door contact Built in door contact to disable remote
transmission Alarm if cover is removed
RT isolation card Optional add-on card (FCA1005-D) to
isolate the remote transmission hardware-
wise
Fire control relays Max. number of optional relay units
(Z3B171) that can be mounted inside the
cabinet
Key switch Optional key switch (FCA1007) to provide
operating access instead of access code