Technical Manual

Table Of Contents
A6V10393190_j_en_-- 81
Fault description
LED
Status
Cause / Action
Sounder fault 3 Fast
Any fault on sounder lines is indicated.
See display for detailed information and
check common issues:
- Short / break
- Missing EOL element
- If output is supervised calibrate line
Alarm dialer fault 4 Fast
Fault of alarm dialer line
See display for detailed information and
check common issues:
- Short / break
- Missing EOL element
- If output is supervised calibrate line
12.2 System
Fault description Cause / Action
Set date & time fault. Power down, requires date & time, chapter 6.4.6.
Buzzer does not work. Check the setting, chapter 7.2.12.
12.3 Accessories
Fault description Cause / Action
DC 24 V is too low. Check voltage input '24V In' on the output card(s) 2M2R.
All four outputs from one
output card 2M2R indicate
a fault.
Locate the faulty output card according to chapter 4.6.2.
- Ribbon cable connected properly, chapter 4.6.2.
- Output card programmed, chapter 7.1.4.
The EVAC module
indicates a fault.
Check the following:
- Ribbon cable connected properly, chapter 4.6.3.
- EVAC module enabled, chapter 7.1.4.
Key switch set No indication is given, change the device.
LED indication field No indication is given, change the device.
P
lease contact your service provider
if you cannot eliminate troubles.