6.1.1 Procedure without Alarm verification
The Alarm dialer is activated in the event of a fire alarm.
Press the <ACKNOWLEDGE> button.
If the alarm event is acknowledged, the panel
turns off the panel buzzer.
Access level 2 password is required.
Optional: Silence the sounder lines by pressing
<RESOUND / SILENCE> button.
MAJOR INCIDENT: A real fire emergency
Check if the fire brigade called.
MINOR INCIDENT: No fire alarm
Reset the system to quiescent mode by pressing
<RESET> button.
Access level 2 password is required.
Inform the fire brigade about the actual situation.
Notice
The fire alarm reoccurs if any device remains in fire condition.
1
Normal Operation
Siemens FC12X
22.12.2012 08:08
Fire alarm 1
Zone 1 1/1
Meeting room 1
Fire alarm 1
Zone 1 1/1
Meeting room 1