7.1.2 Output
Configure the output parameters.
Select an output for programming.
Sounder control
Sounder control is used to activate sounder lines.
(EVAC module replaces 'sounder control' with 'EVAC sounder NL'.)
Alarm dialer Alarm dialer is used to transmit the fire alarm to the intervention
force, e.g. fire brigade.
Fault dialer Fault dialer is used to transmit the fault signal to the intervention
force, e.g. service provider.
Fire output
Fire outputs are used to activate / deactivate controls,
e.g. door holders, lifts, air-condition, etc.
EVAC Sounder NL
EVAC sounders are used to activate sounder lines.
This option is available if the EVAC module is implemented.
Enables supervision, creeping open and short for the outputs: 4, 5, 8, 9, 12 and 13.
The line calibration is needed to achieve supervision. As a result of the calibration the line
resistance is indicated and can be proved using your own calculation.
This option is only availible on output cards and if supervision is set.
General Alarm
Output is activated if the alarm condition is fulfilled:
Zone 'Direct' is activated, V1 / V2 is expired, cross zoning 2
nd
zone is
activated.
Active by zone alarm Output is activated if the selected zone(s) is in alarm.
General Alert Output is activated if cross zoning 1
st
zone is in alarm or V1 / V2 time
is running.
Active by zone alert Output is activated if the selected zone(s) is in alarm by cross zoning
1
st
zone or V1 / V2 time is running.
Alert by ext. input Output is activated if one input is activated and programmed as
'activate alert mode'.
Any isolation
Output is activated if any isolation is set.
Any fault Output is activated if any fault condition occurs.
Manned mode
activated
Output is activated if manned mode is activated.
Alarm dialer fault
Output is activated if the alarm dialer fault via input is in fault condition.
Dialer device
confirmation signal
Output is activated if the programmed input is activated.
V1 / V2 is running
(SE function)
Output flash during V1; Output on during V2.
* Options available depending on the selected mode.
This option is available in Alarm and Alert state.
Default on 0.5 sec. off 0.5 sec. Details see chapter 7.2.6.
Pulse
time
Activation
condition*
Calibrate
line
S
upervision
EN 54-13
Mode
Output
1..n
Output