Technical Manual

Table Of Contents
A6V10393190_j_en_-- 61
7.2.8 Set date and time
Set date and time.
7.2.9 Summer / winter time
Automatic switching
If selected, the panel will switch automatically to the summer /
winter time each year.
7.2.10 Manned / unmanned
V1 time Select the reaction time V1, value from 30 sec. - 4 min.
V2 time Select the investigation time V2, value from 1 min. - 10 min.
Allowed time with regards to EN 54-2 is V1+V2 = 10 min.
Automatic switch to
unmanned
Enable the daily switching time.
Switching time
Set the switching time to unmanned.
7.2.11 Service information
The service information is shown in quiescent mode. Insert text as per chapter 7.5,
e.g. FC12x 'address and telephone number'.
7.2.12 Buzzer
On: Enable the panel’s internal buzzer. Comply with EN 54-2
Off: Disable the panel’s internal buzzer. Not comply with EN 54-2
7.2.13 Calibrate line
Calibration for all programmed supervision outputs at once.
Line calibration is needed to achieve supervision. As a result of the calibration, the line
resistance is indicated and can be provided using your own calculation.
Calibrate
line
Buzzer
Service
information
Manned/
unmanned
Summer/
winter time
Set date
& time