Sinteso™ Fire detection system FS20 Modular, networkable fire detection system for detection, evaluation, sounding an alarm, and extinguishing in the event of a fire.
System System overview The diagrams have been simplified and do not include additional network hardware or security components. Permissible applications are described in the A6V101039125 Network Security Guidelines document. Contact your Siemens IT security expert for more information. Fig.
1 Remote access with SintesoView 2 FS cloud applications 3 Customer network 4 Management platform 5 Remote access to management platform 6 Remote access with Sinteso Mobile 7 Router + firewall + virtual private network 8 Fire damper with actuator Transmission of a fault signal Transmission of an alarm signal You will find a detailed labeled version of the diagram above along with further information in the A6V10906627 planning guide, see chapter 'Product documentation'.
Features and Functions ● Control panel range with 7 types of station – Microprocessor-controlled fire detection system – Compact and modular fire control panels for between 252 and 5000 addresses – PC-based operation via Fast Ethernet with SintesoView – Integrated BACnet interface – Free control logic ● – Phased evacuation FCnet/SAFEDLINK networking – Redundant networking – Increased safety (degraded mode) – Fast data transfer of up to 315 kbit/s ● – Maximum of 32 stations Extended networks via FCnet/LAN
Performance characteristics Optimum use of customer resources ● Individual control panels or an entire network can be operated from a customer PC using the 'SintesoView' visualization software ● Redundancy cabling replaced by fail-safe network nodes ● Floor repeater display and terminals operated on the FDnet detector line High system availability ● Remote access via GAP or Siemens Cloud ● Efficient troubleshooting thanks to remote transmission of diagnosis data ● Maximum reliability and secure detection ●
Networking Networking of fire control panels The diagrams have been simplified and do not include additional network hardware or security components. Permissible applications are described in the A6V101039125 Network Security Guidelines document. Contact your Siemens IT security expert for more information. Up to 32 control panels and terminals can be linked to form one FCnet network.
Fig. 3: Backbone 1 Remote access with SintesoView/ Sinteso Touch 2 FS cloud applications 3 Customer network 4 Management platform 5 Remote access to management platform 6 Remote access with Sinteso Mobile 7 Router + firewall + virtual private network Transmission of a fault signal Transmission of an alarm signal You will find a detailed labeled version of the diagram above along with further information in the A6V10906627 planning guide, see chapter 'Product documentation'.
Stations Cross-station features and functions ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● Fast Ethernet interface for a heterogeneous network Processes signals from the detector series Sinteso FD20 as well as from earlier detector series Interface to Siemens danger management system Slots for RS232 and RS485 serial interfaces Floor repeater displays, terminals and alarm devices on the FDnet detector line with power supply via FDnet All detector lines are monitored for ground faults.
FC2020-EZ Housing (Standard) Detector line (FDnet) ● 252 addresses ● 2 loops/4 stubs Properties ● Operating unit (+LED indicator) ● 70 W power supply ● Max. battery capacity 12 Ah Options of the operating unit ● Key switch (Kaba) FTO2005-C1 ● Key switch (nordic) FTO2006-B1 FC2020-AA Housing (Comfort) Detector line (FDnet) ● 252 addresses ● 2 loops / 4 stubs Properties ● Operating unit ● Operating add-on (empty) ● 150 W power supply ● Max.
FC2030 FC2030-AA Housing (Comfort) FDnet detector line: ● 756 addresses ● 2 loops / 4 stubs ● Can be extended with 2 module bus cards Installable module bus cards (option): ● Line card (FDnet/C-NET) FCL2001-A1 or Line card (FDnet/C-NET, P) FCL2008-A1 ● Line card (collective) FCL2002-A1 ● Line card (MS9i) FCL2003-A1 ● Line card (AnalogPLUS) FCL2005-A1 ● Line card (interactive) FCL2006-A1 ● Line card (interactive Ex) FCL2007-A1 ● I/O card (programmable) FCI2008-A1 ● I/O card (horn/monitored) FCI2009A1 ● I/O
FC2040 You will find information on the integrated extinguishing system and the individual extinguishing components that are available in a separate data sheet with the document ID 'A6V10880701'. FC2040-AA Housing (Comfort) Detector line (FDnet) ● 504 addresses ● 4 loops/8 stubs Properties ● Operating unit ● Operating add-on (empty) ● 150 W power supply ● Max.
FC2040-AG Housing (Comfort) Detector line (FDnet) ● 504 addresses ● 4 loops/8 stubs Properties ● Operating unit ● Operating add-on (4xLED indicator) ● 150 W power supply ● Max. battery capacity 25 Ah Options of the operating unit ● Event printer FTO2001-A1 ● Key switch (Kaba) FTO2005-C1 ● Key switch (nordic) FTO2006-B1 FC2040-GA Housing (Large) Detector line (FDnet) ● 504 addresses ● 4 loops/8 stubs Properties ● Operating unit ● 150 W power supply ● Max.
FC2060 FC2060-AA Housing (Large) FDnet detector line: ● Max.
FC2080 You will find information on the integrated extinguishing system and the individual extinguishing components that are available in a separate data sheet with the document ID 'A6V10880701'.
FHA2022-A1 Carrier (19", power supply) ● ● ● ● ● Basic component for the fire control panel FC2080 Guarantees the required energy supply. Mounted on the side wall of the 19" pedestal housing FH2080-AA.
FT2080 FT2080-A1 Fire terminal (Touch) Detector line (FDnet): ● None Features: ● 12" screen (Touch) EN 54-2-compliant Extra components ● Fire terminal board FTI2001 Can be installed in: ● 19" pedestal cabinet with FC2080 ● Housing (Eco) FH2001-A1 ● Rear cover (FT2080) FHA2039-A1 ● Desktop housing (FT2080) FHA2040-A1 ● Third-party housing with rear cover (FT2080) FHA2039-A1 National extensions Extension Country / region Control panel for fire controls ● France Evacuation operating panels ● ● France
Station application FC2020 For smaller-scale applications, e.g., workshops or hotels. Also suitable for more comprehensive systems thanks to flexible networking options. Single-sector extinguishing applications can also be achieved with this station type. FC2030 For medium-sized applications, e.g., for industrial plants, regional banks, or office complexes. As part of a modernization process, for a gradual and seamless transition from older systems to Sinteso. FC2040 For medium-sized applications, e.g.
Application matrix Use FC2020 FC2030 FC2040 FC2060 FC2080 FT2040 FT2080 Smaller applications, such as workshops or hotels ● ○ ● ○ ○ ‒ ‒ Medium-sized applications, such as medium-sized industrial plants, regional banks, or medium-sized office blocks ○ ● ● ○ ○ ‒ ‒ Large applications, such as industrial plants, large office blocks, or production halls ○ ○ ○ ● ● ‒ ‒ Large applications with high redundancy requirements, such as airports, power generation facilities, and shopping m
Type Overview Fire control panels You will find detailed information on the available control panel types and the available variants in the separate data sheet for the respective control panel type and in the system documentation. You will find information on the document ID of the documents in section 'Product documentation [▶ 27]'. FC2020 FC2030 FC2040 FC2060 FC2080 Standard/ Comfort Comfort Comfort/ Large Large 19" pedestal housing Power supply 70 W/150 W 150 W 150 W 150 W Max.
FC2020 FC2030 FC2040 FC2060 FC2080 Integrated outputs for alarm and control: ● RT alarm relay 1 1 1 1 ● RT fault relay 1 1 1 1 ● Monitored alarm output 1 1 1 1 ● Monitored fault output 1 1 1 1 1/4 1/8 2/8 2/8 ‒ 8 8 12 12 ‒ With cover cap/door 430 x 398 x 160 mm 430 x 796 x 183 mm 430 x 796 x 160 mm 430 x 796 x 260 mm 600 x 2200 x 61 5 mm incl.
Fire terminals You will find detailed information on the available terminal types and the available variants in the separate data sheet for the respective terminal type and in the system documentation. You will find information on the document ID of the documents in section 'Product documentation [▶ 27]'.
FT2040 FT2080 Time functions Freely configurable, time-dependent controls with optional weekly switching programs. In the event of site testing or if detector zones are isolated, timeout functions ensure that these detector zones get reactivated. Event memory Up to 13000 events can be called up for each station based on various criteria. Ground fault monitoring All the outgoing detector lines running out from the control panels are monitored for ground faults.
Hardware extension FC2020 FC2030 FC2040 FC2060 FC2080 FT2040 FT2080 I/O card (remote transmission) FCI2007-A1 ‒ ● ‒ ● ● ‒ ‒ I/O card (programmable) FCI2008-A1 ‒ ● ‒ ● ● ‒ ‒ I/O card (horn, monitored) FCI2009-A1 ‒ ● ‒ ● ● ‒ ‒ Sounder module FCA2005-A1 ● ● ● ● ● ‒ ‒ RS232 module (isolated) FCA2001-A1 ● ● ● ● Integrated ● ● RS485 module (isolated) FCA2002-A1 ● ● ● ● Integrated ● ● Fire brigade periphery module (DE) FCI2001-D1 ● ● ● ● ● ‒ ‒ Extingu
Line devices Fire detector ● ● ● ● Fire detectors with the latest generation of evaluation algorithms. Signals are processed using ASAtechnologyTM. Time-dependent and process-dependent detection behavior. Maximum detection reliability thanks to unique detector properties.
Sounders and sounder bases (sounders, sounder beacons, voice sounders) ● ● ● ● ● ● ● Operation of the sounders and sounder bases on the FDnet detector line. Supply and communication via FDnet No costly additional cabling required Meets the requirements of the EN 54-3 standard Max.
Floor repeater terminal and floor repeater display ● ● ● ● ● The floor repeater terminal FT2010 and the floor repeater display FT2011 are operated directly on the FDnet detector line. The floor repeater display FT2011 displays messages and events from selected areas of the fire detection system. The floor repeater terminal FT2010 displays messages and events from selected areas of the fire detection system and also enables operation. The responsible customer personnel (e.g.
Product documentation Title Document ID System documentation System description 008836 Product data 008837 Planning 008843 Mounting/Installation 008851 Data sheets FC2020 - fire control panel 009383 FC2030 - fire control panel for modernization A6V10087532 FC2040 - fire control panel 009384 FC2060 - fire control panel (modular) A6V10087844 FC2080 - fire control panel (19", modular) A6V10275515 FT2040 - fire terminal 009386 FT2080 - fire terminal (Touch) A6V10378271 Fire detection syste
Notes Safety CAUTION National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage. ● Observe national provisions and comply with the appropriate safety regulations. Disposal The device is considered an electronic device for disposal in accordance with European Directive and may not be disposed of as domestic waste. ● Use only designated channels for disposing the devices.
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies Document ID 008955_n_en_-- Edition 2021-10-22 © Siemens Switzerland Ltd, 2007 Technical specifications and availability subject to change without notice.