Data Sheet for Product

20
Smart Infrastructure A6V10087532_n_en_
--
2021-10-
22
Technical data
Fire control panel (modular)/(modular, P) FC2030 in housing (Comfort)
Supply Mains voltage AC 115 / 230 V +10/-15 %
Power supply 150 W
Operating voltage DC 21…28.4 V
Operating current Max. 5 A
Battery capacity 2x 12 V, max. 25 Ah
Battery monitoring Yes
Network monitoring Yes
Inputs / outputs Connectable detector series Sinteso
Collective detectors which can be
connected
MS7/9/24, DS11, Synova 600,
SIGMACON
Other addressable detectors which can
be connected
MS9i, interactive, AnalogPLUS
Number of addresses Max. 756
Number of integrated line cards 1
Number of integrated lines:
Loops (with loop extension) or 2 (4)
Stubs 4 (8)
Number of additional lines:
FDnet (4 loops per line card) Max. 8 loops
Collective (8 stubs per line card) Max. 16 stubs
MS9i (2 loops per line card) Max. 4 loops
Interactive (1 loop or stub per line
card)
Max. 2 loops/stubs
Interactive Ex (1 stub per line card) Max. 2 stubs
AnalogPLUS (4 loops or stubs per
line card)
Max. 8 loops/stubs
Integrated inputs/outputs:
Alarm RT relay output 1
Fault RT relay output 1
Monitored alarm outputs 1
Monitored fault outputs 1
Monitored horn outputs 1