Data Sheet for Product

4
Smart Infrastructure A6V10087532_n_en_
--
2021-10-
22
Networking of fire control panels
The diagrams have been simplified and do not include additional network hardware or
security components. Permissible applications are described in the A6V101039125
Network Security Guidelines document. Contact your Siemens IT security expert for more
information.
Up to 32 control panels and terminals can be linked to form one FCnet network. If the FCnet
network is connected to a danger management system via BACnet, up to 16 control panels
and terminals can be networked.
Fig. 2: Sub-net
1 Management platform
2 Remote access to management platform
Transmission of a fault signal
Transmission of an alarm signal
An optical FCnet/LAN network allows up to 14 sub-nets with up to 16 stations to be operated
in one network. A maximum of 64 stations is supported in total.