Sinteso™ Fire control panel FC2040 Compact, pre-assembled fire control panel with integrated, user-friendly operating unit. ● ● ● ● ● ● ● ● ● ● ● 009384_v_en_-2021-10-22 Fire control panel for max.
Features and Functions System The diagrams have been simplified and do not include additional network hardware or security components. Permissible applications are described in the A6V101039125 Network Security Guidelines document. Contact your Siemens IT security expert for more information. System overview Fig.
1 Remote access with SintesoView/ Sinteso Touch 2 FS cloud applications 3 Customer network 4 Management platform 5 Remote access to management platform 6 Remote access with Sinteso Mobile 7 Router + firewall + virtual private network 8 Fire damper with actuator Transmission of a fault signal Transmission of an alarm signal You will find a detailed labeled version of the diagram above along with further information in the A6V10906627 planning guide, see chapter 'Product documentation'.
Fig. 2: Sub-net 1 Management platform 2 Remote access to management platform Transmission of a fault signal Transmission of an alarm signal An optical FCnet/LAN network allows up to 14 sub-nets with up to 16 stations to be operated in one network. A maximum of 64 stations is supported in total.
Fig. 3: Backbone 1 Remote access with SintesoView/ Sinteso Touch 2 FS cloud applications 3 Customer network 4 Management platform 5 Remote access to management platform 6 Remote access with Sinteso Mobile 7 Router + firewall + virtual private network Transmission of a fault signal Transmission of an alarm signal You will find a detailed labeled version of the diagram above along with further information in the A6V10906627 planning guide, see chapter 'Product documentation'.
Control panels General features and functions ● Fast Ethernet interface for a heterogeneous network ● Processes the signals of the Sinteso detector series FD20 ● Floor repeater displays, terminals and alarm devices on the FDnet detector line with power supply via FDnet ● Interface to Siemens danger management system ● Slots for RS232 and RS485 serial interfaces ● All detector lines are monitored for ground faults ● Integrated degraded mode function ● Freely configurable, time-dependent controls with optiona
FC2040-AE Housing (Comfort) FDnet detector line: ● 504 addresses ● 4 loops/8 stubs Features: ● Operating unit ● Operating add-on (2xLED indicator) ● 150 W power supply ● Max. battery capacity 25 Ah Operating unit options: ● Event printer FTO2001-A1 ● Key switch (Kaba) FTO2005-C1 ● Key switch (nordic) FTO2006-B1 FC2040-AG Housing (Comfort) Detector line (FDnet) ● 504 addresses ● 4 loops/8 stubs Properties ● Operating unit ● Operating add-on (4xLED indicator) ● 150 W power supply ● Max.
Extensions You will find information on the integrated extinguishing system and the individual extinguishing components that are available in a separate data sheet with the document ID 'A6V10880701'.
FH2004-A1 Housing (Large Extension) ● ● ● ● Empty housing for free use 430 x 398 x 265 mm E.g., for extra batteries, operating add-ons, or event printer Space for the following battery configurations: – 2x FA2007-A1 (45 Ah) or ● FH2005-A1 – 2x FA2008-A1 (65 Ah) The mounting kit for the batteries FHA2061-A1 must be ordered separately. Housing (Large) ● ● ● ● Empty housing for free use 430 x 796 x 265 mm E.g.
Use For medium-sized applications, e.g., for industrial plants, regional banks, or office complexes. Also suitable for more comprehensive systems thanks to flexible networking options.
Setup Fig. 4: FC2040 Comfort Position Designation Type Comment Items 1-5: Basic equipment for each FC2040xx (Comfort). The periphery board (4 loops, P) can be ordered separately to convert the station to the 1.5 A FDnet line. Basic equipment 1 Housing (Comfort) FHA2003-A1 2 Periphery board (4 loops) FCI2004-A1 Periphery board (4 loops, P) FCI2024-A1 3 Power supply (SV 24 V-150 W) V24230-Z6A5 4 Mains terminals on TS35 DIN rail - Space for socket, relay modules, etc.
Position Designation Type Comment 11 Loop extension (FDnet) FCI2003-A1 For loop extension of the periphery board (4 loops) FCI2004-A1 from two to four loops, number of addresses remains the same Loop extension (FDnet/C-NET, P) FCI2025-A1 For loop extension of the periphery board (4 loops, P) FCI2024-A1 from two to four loops, number of addresses remains the same 12 RS485 module (isolated) FCA2002-A1 For peripheral devices with RS485 interface 13 RS232 module (isolated) FCA2001-A1 For device
Type Overview Housing (Comfort) Type FC2040-AA FC2040-AE Number of FDnet addresses Housing (Large) FC2040-AG FC2040-GA 504 Number of lines: Loops (with loop extension) or 4 (8) Stubs (with loop extension) 8 (16) Power supply 150 W Max.
Details for ordering Control panels Type Designation Weight Order number FC2040-AA Fire control panel (4 loops) 14.975 kg A5Q00016100 FC2040-AA Fire control panel (4 loops, P) 16.607 kg S54400-C35-A1 FC2040-AE Fire control panel (4 loops) 15.235 kg A5Q00016852 FC2040-AG Fire control panel (4 loops) 15.524 kg A5Q00016854 FC2040-GA Fire control panel (4 loops) 19.
Auxiliary power supply Type Designation FP2004-A1 Power supply kit (150 W, A) for 1.286 kg EN-compliant installation in empty housing Weight Order number A5Q00020825 FP2005-A1 Power supply kit (150 W, B) for extension 1.181 kg A5Q00018779 Network (backbone) Type Designation Weight Order number FCA2031-A1 Connection module (MoNet) 0.081 kg incl. cable S54400-A153-A1 FHA2029-A1 Mounting kit (switch) 1.261 kg S54400-B79-A1 FN2012-A1 Ethernet switch (modular) 0.
Product documentation Title Document ID System documentation System description 008836 Product data 008837 Planning 008843 Mounting/Installation 008851 System data sheet FS20 – Fire detection system 008955 Data sheets FC2020 - fire control panel 009383 FC2030 - fire control panel for modernization A6V10087532 FC2040 - fire control panel 009384 FC2060 - fire control panel (modular) A6V10087844 FC2080 - fire control panel (19", modular) A6V10275515 FT2040 - fire terminal 009386 FT2080 -
Technical data Fire control panel (4 loops)/(4 loops, P) FC2040 in housing (Comfort) Supply Inputs / outputs Mains voltage AC 115 / 230 V +10/-15 % Power supply 150 W Operating voltage DC 21…28.4 V Operating current Max. 5 A Battery capacity 2x 12 V, max. 25 Ah Battery monitoring Yes Network monitoring Yes Connectable detector series Sinteso (FDnet ) Number of addresses Max.
Fire control panel (4 loops)/(4 loops, P) FC2040 in housing (Comfort) Approvals 18 Smart Infrastructure VdS G206110 LPCB 126bn/03 FM 3048514 DNV GL (marine) MEDB00003UW, See document A6V10400920 009384_v_en_-2021-10-22
Fire control panel (4 loops)/(4 loops, P) FC2040 in housing (Large) Supply Inputs / outputs Mains voltage AC 115 / 230 V +10/-15 % Power supply 150 W Operating voltage DC 21…28.4 V Operating current Max. 5 A Battery capacity 2x 12 V, max. 45 Ah Battery monitoring Yes Network monitoring Yes Connectable detector series Sinteso (FDnet ) Number of addresses Max.
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies Document ID 009384_v_en_-- Edition 2021-10-22 © Siemens Switzerland Ltd, 2007 Technical specifications and availability subject to change without notice.