User Manual

17
Building Technologies
A6V10275515_h_en_
--
Fire Safety 2018-09-28
Technical data
FC2080 inside 19" housing
Supply
Mains voltage AC 115/230 V +10/-15 %
Power supply >150 W
Operating voltage DC 21…28.4 V
Operating current >3 A
Battery capacity 2x 12 V, max. 100 Ah
Battery monitoring Yes
Network monitoring Yes
Inputs / outputs
Connectable detector series Sinteso, collective, MS9i, DS11
Number of addresses Max. 5000
Number of lines in the maximum configuration:
FDnet (4 per line card) Max. 120
Collective (8 per line card) Max. 240
MS9i (2 per line card) Max. 60
Interactive (1 per line card) Max. 30
Interactive, Ex (1 per line card) Max. 30
AnalogPLUS (4 per line card) Max. 120
Input/output cards:
I/Os (programmable) 12 per FCI2008-A1
I/Os (horn) 8 per FCI2009-A1
I/Os (RT):
RT alarm (monitored and relay) 1 + 1 per FCI2007-A1
RT fault (monitored and relay) 1 + 1 per FCI2007-A1
Local alarm 1 per FCI2007-A1
Interfaces
Operating unit optional
RS232, RS485 serial interfaces 1 + 1 (integrated)
Slots for network modules (on CPU and
COM cards)
1 per FCC2004-A1 (Main)
1 per FCC2005-A1 (Degrade)
Slots for module bus cards Max. 37
Ethernet port RJ45 3
Ambient conditions
Operating temperature -8…+42 °C
Storage temperature -20…+60 °C
Air humidity (no condensation
permitted)
95% rel.
Maximum height above sea level 3700 m