User Manual
17
Building Technologies
A6V10275515_h_en_
--
Fire Safety 2018-09-28
Technical data
FC2080 inside 19" housing
Supply
Mains voltage AC 115/230 V +10/-15 %
Power supply >150 W
Operating voltage DC 21…28.4 V
Operating current >3 A
Battery capacity 2x 12 V, max. 100 Ah
Battery monitoring Yes
Network monitoring Yes
Inputs / outputs
Connectable detector series Sinteso, collective, MS9i, DS11
Number of addresses Max. 5000
Number of lines in the maximum configuration:
● FDnet (4 per line card) Max. 120
● Collective (8 per line card) Max. 240
● MS9i (2 per line card) Max. 60
● Interactive (1 per line card) Max. 30
● Interactive, Ex (1 per line card) Max. 30
● AnalogPLUS (4 per line card) Max. 120
Input/output cards:
● I/Os (programmable) 12 per FCI2008-A1
● I/Os (horn) 8 per FCI2009-A1
● I/Os (RT):
RT alarm (monitored and relay) 1 + 1 per FCI2007-A1
RT fault (monitored and relay) 1 + 1 per FCI2007-A1
Local alarm 1 per FCI2007-A1
Interfaces
Operating unit optional
RS232, RS485 serial interfaces 1 + 1 (integrated)
Slots for network modules (on CPU and
COM cards)
1 per FCC2004-A1 (Main)
1 per FCC2005-A1 (Degrade)
Slots for module bus cards Max. 37
Ethernet port RJ45 3
Ambient conditions
Operating temperature -8…+42 °C
Storage temperature -20…+60 °C
Air humidity (no condensation
permitted)
≤ 95% rel.
Maximum height above sea level 3700 m