Installation Instructions

1
Connection module (MoNet) FCA2031-A1
Adjustment elements
8
Siemens Industry, Inc. A6V10407860_a_en_--
Building Technologies Division 2014-04-29
1.4 Adjustment elements
NOTICE
Ground fault supervision
When using the connection module (MoNet) FCA2031, the S33 'Earth-Fault Phy'
switch on the PMI & mainboard must remain OFF. The ground fault detection already
takes place via the MoNet bus.
1.5 Technical data
Supply Voltage System supply DC 24 V
Current Normal operation 0 mA
Maximum current 1 mA
Supply outputs Peripheral data bus DC 20...30 V
SAFEDLINK output DC 20...30 V
MoNet bus DC 20...30 V
Connections Outputs Sockets for ribbon cable
Operating unit Plug-type connection