User Manual

Building Technologies
Fire safety and security products
FCI1802-A2
FC186x Line Card
Product Manual
Characteristics
- FCI1802-A2 line card is specially designed for FC18 series controllers. It can be
automatically identified by controller. It is used for connection with FD181series
field devices.
- A FCI1802-A2 line card contains one line, and each line can connect 252 points.
- 2-wire polarity-free of detection busstub wring is available and free branch is ac-
ceptable.
- Overload protection is available.
- In case of a short circuit line protection is activated automatically. When trouble is
resolved, line card can recover normal automatically.
Technical Data
Max. No. of line for each card 1
Max. No. of field devices for each line 252
Max. No. of load factor for each line 252
Wire type for FD18-BUS Recommend RVS1.0~RVS1.5
Max. distance of loop 2500m
Max. distance of stub 1500m
Line impedance 60Ω(mongline)
Line capacitive reactance 500nF
Auto protection in case of short circuit (isolation) available
Line operating voltage
24VDC
Quiescent current
30mA
Max. current
1.5A
Operating temperature
0 ~ +50
Storage temperature
-20 ~ +60
Humidity
95% (40±2)
Size
155*120mm

Summary of content (3 pages)