Model FC2005 is an addressable FACP that provides a cost-
effective solution for simple fire-alarm-system applications.
Model FC2005 contains one (1) built-in DACT and two (2)
NACs.
Small and compact in design, Model FC2005 is ideal for
small fire-protection applications using no more than 50
addressable points:
retail outlets / strip malls
doctors’ offices
dry cleaners
restaurants
banks, etc.
The dimensions of Model FC2005 (connected to a one-
height-unit enclosure) are approximately as follows:
16.25”[41.3 cm.](H) x 18”[46 cm.](W) x 5”[41.3 cm.] (D)
The weight (without operating unit or batteries) is
approximately 9 Lbs [4082 g].
50-Point System Enclosure
The Model FH901-U2 / R2 enclosure for the Model FC2005
FACP is available in either black or red, and supports all
system modules. The enclosure also supports 12Ah
batteries.
Note: For systems requiring larger than 12Ah batteries, use a
UL Listed battery box.
When field-wiring installation is complete, the main board
shall be moved to the upper position for standard mounting
prior to applying power to the system.
The Model FH901-U2 / R2 enclosure for the 50-point panel is
comprised of a dual-mounting setup that allows the main
board to be partially mounted in a lower-to-upper position.
When temporarily installed in the lower position,
technicians are allowed more space to install field wiring at
the time of system set-up.
Additionally, the enclosure supports an optional battery
bracket (Model FHA901-U1) that can be used to secure
batteries up to 12Ah. Model FHA901-U1 is required to
comply with seismic certification, pursuant to ASC / SEI 7-
05, Section 13.2.2.
A flush-mount trim kit (Model FHA902-U1/R1) is also
available for use when flush mounting Model FH901-U2/ R2.
Remote Annunciator (not approved for use in Canada)
Used exclusively with the Desigo 50-point FACP, the Remote
Annunciator (Model FSD901-U2 / R2) shows existing status
of the Model FC2005 FACP.
A built-in RS−485 serves as the interface between the
remote annunciator and the Desigo 50-point FACP. Up to
eight (8) remote annunciators are supported for each 50-
point fire system. A 3.5-inch (8.9 cm) by 1.5” (3.8 cm) LCD
screen will show details of the event in alphanumeric form.
The display screen can be scrolled to reveal additional
events. Each screen supports 182 characters: seven (7)
lines with 26 characters per line.
Remote Peripheral Module (with RS485 interface)
The Remote Peripheral Module (FCA2018-U1) provides a
means of connecting a Desigo panel to a parallel printer for
creating a hard copy of system-status and configuration
reports. This supervised, intelligent module contains built-
in transient protection and plain-decimal addressing.
Model FCA2018-U1 is remotely connected to the Model
FCA2016-U1 RS485 communication bus from any Desigo
system enclosure. Model FCA2018-U1 uses Class B (Style
4) or Class A (Style 6) wiring, and provides two (2) RS232
(serial) ports and a single parallel port that allow connection
to the parallel printer (Model PAL-1).
When Model PAL-1 is used with the remote peripheral
module, Model FCA2018-U1 supervises the printer for On /
Off Line, Power On, Paper Out, Paper Jam, and wiring-fault
conditions, as required by UL for NFPA 72 proprietary
systems. Event and report printing is generated at the
operating unit on the main Desigo system.
Leased-Line / City-Tie Module
The Leased-Line / City-Tie module (Model FCI2020-U1) is
used as an optional module, providing a local-energy output
for municipal call-box connection.
Model FCI2020-U1 also gives a reverse-polarity output for
leased-line connection. Model FCI2020-U1 is installed on
the back of the main board of the Model FC2005 FACP.
When used for connection to a municipal call box, the city-
tie function supports Alarm-event transmission. When used
for leased-line connection, the module supports two (2)
leased telephone lines for transmitting Alarm, Trouble and
Supervisory events.
Model FC2005
Model
FSD901-U2
Desigo 50-Point Fire System
50-point System Components
50-point System Components