Data Sheet for Product

Siemens Data Sheet 9800
Smart Infrastructure Building Products usa.siemens.com/fire
Cerberus PRO, a comprehensive fire-
protection system from Siemens
Fire Safety, is a technologically
advanced fire-and-life-safety
system. Each Cerberus PRO system
provides easy operation via its push-
button soft keys; a backlit LCD
screen, and a (4) four-way
navigation push button all located
in the upper portion of each panel.
Through the use of its unique
multiprocessor ’Network’ design
along with its ability to utilize
intelligent detection devices
Cerberus PRO epitomizes a flexible
and highly configurable fire system.
Cerberus® PRO
A Comprehensive Fire-Protection
System
Architect & Engineer Specifications
Standard 50-point, 252-point and 504-point fire systems
Remote viewing for the 252-point and 504-point systems
One (1) or (2) two-height-unit enclosures
Powerful, but user-friendly system interface
Softkey buttons
RS485 interface
Four-way navigation menu with extended-views
capability
Primary, regulated power
300-Watts is rated at 11.5 Amps
170-Watts is rated at 6.5 Amps
Universal AC power input:
120VAC or 240VAC
50 / 60Hz @ 2.0A max
Fully field programmable, via a Windows®-laptop PC
Built-in strobe synchronization protocol
Global annunciation and control capability
Several relay commands:
Alarm, Trouble, Supervisory, etc.
Light-emitting diodes (LEDs) for:
Power, Alarm, Supervisory, Silenced, Ground Fault,
Trouble, and system-status LEDs
- Alarm command has a larger, distinctive LED
LED-option provides LED annunciation of system activity
Backlit liquid-crystal display (LCD)
SureWire
TM
addressable-loop technology
- Patented polarity-insensitive detection circuits
Intelligent / analog detection circuits: ‘Class A’ orClass B
Supports FirePrint
TM
detection applications
Supports single-person, ‘Walk Test’
Sprinkler Supervision
End-user ‘Help’ screens
Multiple command stations
Supports pre-action, deluge and Sinorix®-agent releasing
for 252 / 504-point systems
- Releasing-valve monitoring
10,000 event history / event log
Detector Sensitivity Readout / Printout per NFPA 72
ISOtechnology device compatibility including PAD-5
addressable NAC power supply
Network up to 32 panels using SafeDLink / CV Web
Cerberus PRO
Fire Alarm Panel
Cerberu DMS Danger Management Station can monitor,
control up to 16 Model FC922, FC924 FACPs
Supervised remote printer, via the Remote Peripheral Module
for the 252 / 504-point systems
Menu-driven operator commands
10,000-event history-logging capability with on-line and
off-line reports
- Off-line reports can be viewed the custom-configuration
programming tool
- EEPROM software compatible
Multiple levels of password protection
Automatic environmental compensation for smoke detectors
Pre-alarm operation
Alarm verification (by device or zone)
Degrade-mode operation
Logic-controlled output functions
Optional city-tie / leased-line module
Distributed processing
Gas Alarm events for CO detection, per NFPA 720 for the 252 /
504-point systems
Optional notification-appliance-circuit (NAC) expansion module
Up to 3.0 amps (24VDC) load per output
Module used for 252/ 504-point systems
NEC 760 power-limited circuits
UL 864-compliant, UL 864 10
th
Edition Listed, ULC-S527 Listed
FM (#3010), CSFM (#7165-0067:0259) and FDNY (#6104)
Approved
Supports built-in TCP/IP Connectivity
Cerberus PRO System Overview

Summary of content (10 pages)