Data Sheet for Product

4
usa.siemens.com/fire
Power Supply Modules (cont.)
The 170-Watt power supply incorporates a 4.0A, non-
resettable slow-blow fuse on the primary input, and
includes a built-in AC-line filter for surge and noise
suppression. Model FP2011-U1 mounts in a standard
Cerberus PRO-brand enclosure, and there are no serviceable
parts to be maintained.
The 300-Watt power supply incorporates two (2) 6.3A
replaceable, non-resettable slow-blow fuses on the primary
input and includes a built-in AC-line filter for surge and noise
suppression. Model FP2012-U1 mounts in a Cerberus PRO-
brand enclosure, and there are no serviceable parts to be
maintained.
Model FP2011-U1 is used with Models FC901, FC922 and
FC924 FACPs. Model FP2012-U1 operates with Models
FC922 and FC924 FACPs.
NAC Expansion Module
The NAC expansion module (Model FCI2011-U1) is an
optional module that is connected to the peripheral boards
(Models FCI2016-U1, FCI2017-U1), providing additional
NACs to 252-point and 504-point systems, respectively.
One (1) ‘Class A’ or two (2) ‘Class B’ NACs are provided with
the following Cerberus PRO systems:
Model FC922 (252-point)
Model FC924(504-point)
Each NAC is rated at 3 Amps. Each NAC expansion module is
monitored for open-line and short-circuit conditions.
Releasing Module
The Cerberus PRO releasing module (Model XCI2001-U1) is
an optional module that is connected to the peripheral
boards (Models FCI2016-U1, FCI2017-U1), providing two (2)
circuits of optional releasing, respectively.
Releasing Module (cont.)
Model XCI2001-U1 supports activation of releasing valves
in pre-action / deluge systems (including double-interlock
pre-action systems, or Sinorix engineered fire suppression
systems). Model XCI2001-U1 supports only ‘Class B’
releasing circuits.
When installed on a Model FC922 or Model FC924
Cerberus PRO FACP, the releasing module contains an
integral manual-disconnect switch for releasing circuits.
This essential feature protects the releasing circuits from
accidental discharge during maintenance.
Activation can be accomplished via cross zoning of
automatic detectors or manual activation within one (1)
FACP.
A pre-discharge countdown timer is available for display at
the operating unit (Model FCM2018-U3 or Model
FCM2019-U3).
Remote Peripheral Module (with RS485 interface)
The Remote Peripheral Module (FCA2018-U1) provides a
means of connecting a Cerberus PRO panel to a parallel
printer for creating a hard copy of system-status and
configuration reports. This supervised, intelligent module
contains built-in transient protection and plain-decimal
addressing.
Model FCA2018-U1 is remotely connected to the Model
FCA2016-U1 RS485 communication bus from any
Cerberus PRO system enclosure. Model FCA2018-U1 uses
Class B (Style 4) or Class A (Style 6) wiring, and provides
two (2) RS232 (serial) ports and a single parallel port that
allow connection to the parallel printer (Model PAL-1).
When Model PAL-1 is used with the remote peripheral
module, Model FCA2018-U1 supervises the printer for On /
Off Line, Power On, Paper Out, Paper Jam, and wiring-fault
conditions, as required by UL for NFPA 72 proprietary
systems. Event and report printing is generated at the
operating unit (Model FCM2018-U3 or Model FCM2019-
U3) on the main Cerberus PRO system.
252 / 504-point System Components
Model
XCI2001-U1
Model
FCI2011-U1
Model
FCA2018-U1