Data Sheet for Product

7
usa.siemens.com/fire
LED-Option Module (cont.)
Model FCM2023-U3 is a LED-option module that provides
LED annunciation of system activity.
The LED-option module can either be configured up to 24
indicator zones, or is capable of displaying up to 48
individual LEDs. Each zone contains :
One (1) RED / GREEN bi-color LED
One (1) YELLOW LED
For Model FCM2034-U3, each zone contains:
One (1) RED / YELLOW bi-color LED
One (1) YELLOW LED.
Any event can be assigned to each LED, which may be
configured as a ‘static or ‘flashing’ indicator using the
Cerberus PRO custom-configurable software tool, ‘Cerberus
Works’. Normally, the LED indicator is used as a zone
indicator.
The LED-option module is connected to the peripheral data
bus, and can be cascaded to up to a maximum of four (4)
LED modules. A space is provided for labeling of LED
functions. The label slides behind a clear, protective
membrane.
Blank Option Module
Model FCM2022-U3 is a blank-option module intended to
cover any blank LED areas where LED modules are not
being occupied.
Models FCM2022-U3, FCM2023-U3 and FCM2034-U3 are
mounted on the inner door of a Cerberus PRO enclosure.
Any combination of modules may be mounted on the inner
door. Up to four (4) total modules can be supported.
The Battery Disconnect Module
The Battery Disconnect Module (Model FCA2032-U1) is
specifically designed to disconnect the backup battery on
the Cerberus PRO 252 / 504-point addressable FACP when
battery voltage drops below 19VDC. The disconnection
caused by Model FCA2032-U1 prevents the battery from
discharging beyond the power level of normal system
operation.
The battery-disconnect module, which is mounted next to
the DACT, remains disconnected until AC power is restored
to Models FC922 and FC924.
S-Series License Keys
The S1 license key (Model FCA2033-A1) allows for virtual
monitoring and control between a Cerberus PRO fire-only
panel and a personal computer.
The S2 license key (Model FCA2034-A1) is a BACnet output,
and is used for monitoring-only purposes by
a 3rd-party system for life-safety objects.
S-Series License Keys (cont.)
The S3 license key (Model FCA2035-A1) is a combination
license key that allows for virtual monitoring and control, as
well as for distribution of BACnet (monitoring-only)
communications. A four-digit personal identification
number (PIN) must be used in order to prevent
unauthorized access.
Legacy Migration Hardware Kit
The Cerberus PRO 922/924 panel offers support for
Siemens legacy addressable and conventional systems.
Model FHA2056-series kits are specifically designed for the
seamless transition of an existing Siemens FS-250
(FireSeeker) or MPC6000 control panel into a fully
operational 50 | 252 or 504-point addressable Cerberus
PRO fire-alarm FACP, [FC901 | FC922 or FC924,
respectively].
Each shipment of the Model FHA2056-series kits contains
the following pieces of equipment:
One (1) outer door
One (1) inner door
One (1) hinge-assembly bracket
One (1) back plate
One (1) inner-door bracket
NOTE: The five (5) items that comprise one (1) Model FHA2056-
series hardware-migration kit cannot be ordered individually.
Model FHA-MIQKIT-04/-05 offers support for legacy MXL
and MXL-IQ peripherals using the FCL2004 device interface
module. This allows the user to configure a Cerberus PRO
panel to communicate to older addressable devices,
offering a seamless migration solution to the latest
technology system.
252 / 504-point System Components
Model
FHA-MIQKIT