Data Sheet for Product
Leased-Line / City-Tie Module
6810
s Industry, Inc.
Building Technologies Division
s
Data Sheet
Fire Safety Products
Desigo® Fire Safety System
Leased-Line / City-Tie Module
Model FCI2020-U1
Product Overview
Model FCI2020-U1 is used as an optional
module, giving a local-energy output for
municipal call-box connections. Additionally, a
leased-line / city-tie module provides reverse-
polarity output for leased-line connections.
Model FC
I2020-U1 is installed on the 252-point
(Model FC
I2016-U1) and 504-point (FCI2017-
U1) periphery boards, respectively, but is
installed on the back of the main board (Model
FCM901-U2) used with Desigo 50-point
addressable panels.
When an optional leased-line / city-tie module is
used on Desigo 50-point panels, a wiring harness
(Model FCA901-U1) must be ordered separately.
When used for connection to a municipal call
box, the city-tie function supports Alarm-event
transmission. When used for leased-line
connection, the module supports two (2) leased
telephone lines for transmitting Alarm, Trouble
and Supervisory system events.
The Leased-Line / City-Tie Module is FM (
#
3010); CSFM
(
#
7165-0067:0259), and FDNY (
#
6104) Approved.
Additionally, the programming software is held in flash
electrically erasable programmable read-only memory
(EEPROM).
Temperature and Humidity Range
Model FCI2020-U1 is UL 864 9
th
Edition Listed for
indoor dry locations within a temperature range of 120
+
/
-
3°F (49
+
/
-
2°C) to 32
+
/
-
3°F (0
+
/
-
2°C) and a relative
humidity of 93
+
/
-
2% at a temperature of 90
+
/
-
3°F (32
+
/
-
2°C).
Related Documentation
Product Data Sheet
Number
FC2005
(50-point addressable panel)
6813
F
C
2025
(252-point addressable panel)
6815
FC2050
(504-point addressable panel)
FV2025
(252-point intelligent voice addressable panel)
6821
FV2050
(504-
point intelligent voice addressable panel)
•
Connects a Desigo Fire Safety System
to a municipal call box
All connections are supervised by all Desigo
(fire and intelligent voice communication) systems
Installed on the Model FC2005 fire-alarm control panel’s
(FACP) main board, Model FCM901-U2
Installed on Desigo 252-point (Model FCI2016-U1) and
504-point (Model FCI2017-U1) periphery boards
•
Provides system-event data over leased
telephone lines
•
Power-limited protection
•
UL 864 9
th
Edition Listed, ULC Listed;
FM, CSFM and NYC Fire Department Approved
ARCHITECT AND ENGINEER SPECIFICATIONS