Data Sheet for Product
ARCHITECT AND ENGINEER SPECIFICATIONS
Data Sheet
Leased-Line / City-Tie Module
Model FCI2020-U1
Answers for infrastructure
Cerberus
PRO
Fire Safety Products
Cerberus PRO
9810
Leased-Line / City-Tie Module
Produ ct Overview
Model FCI2020-U1 is used as an optional
module, giving a local-
energy output for
municipal call-box connections. Additionally,
each leased-line / city-
tie module provides
reverse-polarity output for leased-line
connections.
Model FCI2020-U1 is installed on the 252-point
(Model FCI2016-U1) and 504-point (Model
FCI2017-U1) periphery boards, respectively, but
is installed on the back of the main board (Model
FCM901-U3) used with Cerberus PRO 50-point
addressable panels.
When an optional leased-line / city-tie module is
used on Cerberus PRO 50-point panels, a wiring
harness (Model FCA901-U1) must be ordered
separately.
When used for connection to a municipal call
box, the city-tie function supports Alarm-event
transmission. When used for leased-line
connection, the module supports two (2) leased
telephone lines for transmitting Alarm, Trouble
and Supervisory events.
The Leased-Line / City-Tie Module is FM (
#
3010);
FDNY (
#
6104) and CSFM (
#
7165-0067:0259)
Approved. Additionally, the programming software is
held in flash electrically erasable programmable read-
only memory (EEPROM).
Temperature and Humidity Range
Model FCI2020-U1 is UL 864 9
th
Edition Listed for
indoor dry locations within a temperature range of
120
+
/
-
3°F (49
+
/
-
2°C) to 32
+
/
-
3°F (0
+
/
-
2°C) and a
relative humidity of 93
+
/
-
2% at a temperature of
90
+
/
-
3°F (32
+
/
-
2°C).
Related Documentation
Product Data Sheet
Number
FC901
(50-point addressable panel)
9813
FC922
(252-point addressable panel)
9815
FC924
(504-point addressable panel)
FV922
(252-point intelligent voice addressable panel)
9821
FV924
(504-point intelligent voice addressable panel)
•
Connects a Cerberus PRO system
to a municipal call box
All connections are supervised by all Cerberus PRO
(fire and intelligent voice communication) systems
Installed on the Model FC901 fire-alarm control
panel’s (FACP) main board, Model FCM901-U3
Installed on Cerberus PRO 252-point (Model FCI2016-U1)
and 504-point (Model FCI2017-U1) periphery boards
• Provides system-event data over
leased telephone lines
•
Power-limited protection
•
UL 864 9
th
Edition Listed, ULC Listed;
FM, CSFM and NYC Fire Department Approved