User Manual
10
Smart Infrastructure A6V10725075_en--_d
2019-10-25
Functional data
Tones ● 16 tones (including school bell)
● 2 alarm levels ('Warning' and 'Evacuation')
● 3 sound levels (maximum / medium / minimum)
Voice messages ● 5 standard voice messages in 15 languages
● Max. 7 events
● 3 sound levels (maximum / medium / minimum)
● Each voice message can be emitted in two
languages
Sound level (alarm sound level) FDS224-x, FDS226-x: 75…99 dBA
FDS225-xx, FDS227-xx, FDS227-xx-C: 71…94 dBA
Luminous intensity
1
(according to EN 54-23)
LED white High (W-3.2-10)
Medium (W-2.4-7.5)
Low (O-2-6.2)
(wall mounting, cubic cover cap as for category W)
Indicator: 0.4…5 cd
2
LED red High (W-2.8-8.8)
Medium (W-2.4-7.5)
Low (O-2-6.2)
(wall mounting, cubic cover cap as for category W)
Indicator: 0.3…3 cd
2
Luminous intensity levels
1
4 levels (high/medium/low/indicator)
Communication protocol FDnet/C-NET
System compatibility FDnet/C-NET FS20/FS720
Color ~RAL9010 pure white or
~RAL3000 flame red
1
Only for FDS226-xx, FDS227-xx, FDS227-xx-C
2
Does not comply with EN 54-23
Line connections
Conductor cross section 0.2...2.5 mm
2
Ambient conditions and protection category
Protection category (IEC 60529):
● With base FDB226-x:
● With base deep FDB227-x:
● IP33C
● IP65 (no LPCB approval)
Operating temperature -25...+70 °C
Storage temperature -30...+75 °C
Air humidity ≤95 % rel.