Data Sheet for Product
Siemens Data Sheet 9906
Smart Infrastructure - Building Products usa.siemens.com/fire
Cerberus® PRO
Specialized Devices
Models FDBZ492, FDBZ492-HR, FDBZ492-R and
FDBZ492-PR (with FDBZ-WT and FDBZ492-RTL)
FDBZ-series of air-duct housings
[FDBZ492, FDBZ492-HR, FDBZ492-R & FDBZ492-PR]
Architect & Engineer Specifications
Four (4) models available
Addressable and conventional with and
without relays
Compatible with Siemens ─ Fire Safety
conventional and addressable fire-
alarm control panels (FACPs)
Magnet test feature with the Model
OP121 conventional detector
Design for air-velocity range of 100 to
4,000 feet-per-minute (fpm)
Robust, compatible conventional
remote indicator test switch that
incorporates tri-color light-emitting
diode (LED)
Clear housing cover with smoke test
port on cover for quick identification of
detector type
Removable via four (4) captive-thumb
screws (no tools required)
Includes a smoke / aerosol detector test
port
Optional NEMA 4X-reinforced, stainless-
steel and watertight enclosure
available, Model FDBZ-WT
No tools required for cover removal,
sampling and exhaust-tube installations
Trouble-event activation upon front-
cover removal
Alarm LED visible from front
Self-contained model available with ‘on-
board’ power supply for conventional
detectors
Expanded temperature range
Relay models available
UL268A Listed, ULC-S529 Listed
FM (#3010), CSFM (#3240-0067:0265)
Approved
Product Overview
The Siemens ─ Fire Safety Model ‘FDBZ’-series of air-duct-detector housings are
designed for use with Siemens Model ‘H’-series, Cerberus PRO-series and Model
OP121 detectors. (see: Details for Ordering for a complete list of compatible
devices).
Designed for installation directly to heating, ventilating and air-conditioning
(HVAC) duct systems, the Model ‘FDBZ’-series of duct housings complies with
National Fire Protection Association Standard (NFPA) No.’s 72 and 90A, and is
Underwriters’ Laboratories Listed.
When equipped, the air-duct detector housing will signal the presence of smoke
being carried through the duct system. Air-duct detectors are not intended to be
substituted for open-area detection.
Notes: Most conventional time-control equipment guarantee only one (1) detector
per zone when the detector’s operated relay function is critical. The connection of
a remote lamp and a remote relay −per detector − is allowed. Refer to the
installation manual of the respective conventional FACP. With either the Cerberus
PRO series or FireFinder® XLS series of FACPs, up to 252-addressable detectors with
relays per circuit may be used. The connection of an intelligent remote lamp (ILED)
and a remote relay is allowed for each detector simultaneously.
Specifications
The Model ‘FDBZ’-series of air-duct housings are uniquely designed to use with the
photoelectric detector. Sensitivity of Models PE-11, PE-11C, OP121, and 8854
conventional detectors can be verified for calibration via LED visual status or a
Model RSAW-11, Model RSAC-11 or FDBZ492-RTL multi-color remote lamp. A
green flash indicates the detector has passed its self-test. Amber indicates a
Trouble condition, and red indicates an Alarm event.
Sensitivity for Models FP-11, HFP-11, SFP-11, HFPO-11, SFPO-11, OP921, OOH941,
OOHC941, 8710, and 8713 intelligent detectors is verified from the multi-color
LED of the respective detector, or its sensitivity reading may be printed by
command from the corresponding FACP to an optional printer.