Data Sheet for Product
Siemens
Smart Infrastructure - Building Products
–3–
usa.siemens.com/fire
Operation
Based on the monitoring results, the LED indicator flashes the following colors based on the following conditions:
*LED can be turned OFF.
Please follow the corresponding description of the panel used.
Flash Color
Condition
Flash
Interval
(in seconds)
Green*:
Normal supervisory operation. Smoke sensitivity is within
rated limits.
10
Yellow:
Detector is in Trouble condition, and needs either repair or
replacement.
4
Red:
Alarm condition.
1
No Flash:
Detector is not powered.
─ ─
Operating Temperature
Ranges:
+32°F (0°C) to 120°F (49°C)
Sampling Tube Pressure
Range of Differences:
> 0.01 inches - < 1.2 inches of
water column
Relative Humidity:
0 - 95%; non-condensing
Air Pressure:
No effect
Altitude Range:
No limitations
Air-Duct Velocity:
100 ─ 4,000 ft. / min
(0.51─ 20m / sec)
Dimensions:
(H -x- W -x- D)
Rectangular:
14.38” -x- 5” -x- 2.5”
(37 cm. -x- 12.7 cm. -x- 6.36 cm.)
Square:
7.75” -x- 9” -x- 2.5”
(19.7 cm. -x- 22.9 cm. -x- 6.36 cm.)
Detector Weight:
1.8 Lbs. (0.82 Kg.)
▪ Short-Return (outlet) Tube
▪ Stopper
▪ #12 + 3/4” Sheet-Metal Screws
▪ Mounting Template
Note: Detector and Sampling Tube to be purchased separately. Minimum
hardware required:
− one (1) Air-Duct Housing Assembly
− one (1) Sampling Tube
− one (1) Detector
Technical Data
Physical Properties
Air Duct Housing Hardware Package