Data Sheet for Product

ARCHITECT AND ENGINEER SPECIFICATIONS
Data Sheet
Models FDBZ492, FDBZ492-HR, FDBZ492-R and FDBZ492-RP {with FDBZ-WT and FDBZ-RTL}
Specialized Devices
Air-Duct Housings (FDBZ Series)
Product Overview
The Siemens Fire Safety Model ‘FDBZ-series of air-
duct-
detector housings are designed for use with
Siemens Model ‘H’-series, Cerberus PRO-series and
Model OP121 detectors (see: Details for Ordering for
a complete list of compatible devices).
Designed for installation directly to heating, ventilating
and air-conditioning (HVAC) duct systems, the Model
‘FDBZ’-series of duct housings complies with National
Fire Protection Association Standard (NFPA) No.’s 72
and 90A, and is Underwriters’ Laboratories Listed.
When equipped, the air-duct detector housing will
signal the presence of smoke being carried through
the duct system. Air-duct detectors are not intended
to be substituted for open-area detection.
Notes: Most conventional time-control equipment guarantee
only one (1) detector per zone when the detector’s
operated relay function is critical. The connection
of a remote lamp and a remote relay per detector
is allowed. Refer to the installation manual of
the respective conventional FACP.
Notes
- (cont.’d):
With either the Cerberus PRO series or
FireFinder
®
XLS series of FACPs, up to 252-addressable detectors
with relays per circuit may be used. The connection of an intelligent
remote lamp (
ILED) and a remote relay is allowed for each detector
simultaneously.
Specifications
The Model ‘FDBZ’-series of air-duct housings are uniquely
designed to use with the photoelectric detector.
Sensitivity of Models PE-11, PE-11C and OP121 detectors
can be verified for calibration via LED visual status or a
Model RSAW-11, Model RSAC-11 or FDBZ-RTL multi-color
remote lamp. A
green flash indicates the detector has
passed its self test. Amber indicates a Trouble condition,
and red indicates an Alarm event.
Sensitivity for Models HFP-11, FP-11, SFP-11, HFPO-11,
SFPO-11, OP921, OOH941 and OOHC941is verified from
the multi-
color LED of the respective detector, or its
sensitivity reading may be printed by command from the
corresponding FACP to an optional printer.
9906C
Model `FDBZ’ Series of Air-Duct Housings and Detectors
Cerberu
PRO
Fire Safety Products
Four (4) models available
Addressable and conventional with and without relays
Compatible with various Siemens Fire Safety
fire-alarm control panels (FACPs)
Magnet test feature with the Model OP121
conventional detector
Design for air-velocity range of 100
to 4,000 feet-per-minute (fpm)
Robust, compatible conventional remote indicator test
switch that incorporates tri-color light-emitting diode (LED)
Clear housing cover with smoke test port on cover
for quick identification of detector type
Removable with only four (4) captive-thumb screws (no tools required)
Includes a smoke / aerosol detector test port
Optional NEMA 4X-reinforced, stainless-steel and
watertight enclosure available, Model FDBZ-WT
No tools required for cover removal, sampling and
exhaust-tube installations
Trouble-event activation upon front-cover removal
Alarm LED visible from front
Remote alarm
indicator
[FDBZ-RTL]
FDBZ-series of air-duct housings
[FDBZ492, FDBZ492-HR, FDBZ492-R and FDBZ492-RP]
Watertight housing
[FDBZ-WT]
Self-contained model available with ‘on-board’
power supply for conventional detectors
Expanded temperature range
Relay models available
UL268A Listed, ULC-S529 Listed;
FM (#3010), CSFM (#3240-0067:0265) Approved

Summary of content (4 pages)