3.2.4 Adjustment elements
The multi line separator module has four jumpers, J1...J4. These jumpers can be
used to configure whether the FDCL221-M is to be operated in one FDnet/C-NET
loop or two FDnet/C-NET loops.
Jumpers J1...J4 have the following two plug positions:
1-loop operation 2-loop operation
The jumpers are plugged on 1-loop operation when delivered.
See also
2 Function [ 19]
3.3 Function
The multi line separator module FDCL221-M has several electronic switches
(line separators). The following operation modes can be configured using jumpers:
1-loop operation
(9 line separators in one FDnet/C-NET loop)
2-loop operation
(4 line separators each in two FDnet/C-NET loops)
The function of the line separator in the FDnet/C-NET loop is to connect sub-stub
lines to the FDnet/C-NET and selectively disconnect them in the event of a short-
circuit. In the event of a short-circuit the line separator disconnects the affected bus
area in the FDnet/C-NET so that the area unaffected by the short-circuit continues
to function.
The multi line separator module has 2 x 4 screw terminals for the FDnet/C-NET
loops and a 20-pin connector with socket strip for the ten sub-stub lines. A
maximum of two different loops can be connected.
The status of each line separator is indicated by a yellow LED. The LED flashes if
the line separator is open or in localization mode.
The multi line separator module is installed in the intermediate distributor or directly
in the fire control panel.
NOTICE
Incorrect use
False alarm caused by potentials moving in the event of external supply on the
sub-stub via a FDnet/C-NET card.
Sub
-
stubs may only be fed via the line separator.
J1
J2
J3
J4
1 2 3
J1
J2
J3
J4
1 2 3