User Manual

Specifications
Technical data
8
37 |
42
Building Technologies
A6V10224006_g_en_
--
Fire Safety
2018
10
25
Line separator
(per separator)
Line voltage:
Nominal DC 32 V (= V
nom
)
Minimum DC 12 V (= V
min
)
Maximum DC 33 V (= V
max
)
Voltage at which the separator
opens:
Minimum DC 7.5 V (= V
SO min
)
Maximum DC 10.5 V (= V
SO max
)
Permanent current when switches
are closed
Max. 1.5 A (= I
C max
)
Switching current (e.g., in the
event of a short-circuit)
Max. 2 A (= I
S max
)
Leakage current when switches
are open
Max. 1 mA (= I
L max
)
Serial impedance when switches
are closed
Max. 0.4 Ω (= Z
C max
)
When operated on the FDnet/C-NET, the line separator is closed via an
actuation signal from the control panel. Required line voltage: DC 12...33 V
(normal range)
External alarm indicators
Number of external alarm
indicators that can be connected
None
Connections Detector line:
Design Screw terminals on plug
Cable cross section 0.2…1.5 mm
2
Bare length 6 mm
Sub-stubs:
Design Socket strip
Cable cross section 0.2…1.5 mm
2
Bare length 10 mm
Ambient conditions Operating temperature -25…+70 °C
Storage temperature -30…+75 °C
Air humidity (non-condensing) 95 % rel.
Protection category (IEC 60529):
Without housing IP30
With housing FDCH221,
screwed
IP65
Electromagnetic compatibility:
1 MHz…2 GHz 10 V/m