FDCL221 Line separator Technical Manual 007063_h_en_-2019-07-04 Smart Infrastructure
Imprint Imprint Technical specifications and availability subject to change without notice. Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders will be held liable for payment of damages. All rights created by patent grant or registration of a utility model or design patent are reserved. Issued by: Siemens Switzerland Ltd.
Table of contents 1 1.1 1.2 1.3 1.4 About this document ............................................................................. 5 Applicable documents ................................................................................. 7 Download center ......................................................................................... 8 Technical terms .......................................................................................... 8 Revision history ....................................
| 32 007063_h_en_--
About this document Applicable documents 1 1 About this document Retention and availability NOTICE Missing information Damage due to misuse ● This document must be available in a usable format throughout the entire life cycle of the product. Keep the document for reference and ensure that it can be accessed by target groups. Should you require another copy of this document, please contact the Customer Support Center, phone +49 89 9221-8000.
1 About this document Applicable documents Target groups The information in this document is intended for the following target groups: Target group Activity Qualification Product Manager ● ● ● Project Manager ● ● Project engineer ● ● ● Installation personnel ● ● Maintenance personnel ● ● ● Is responsible for information passing between the manufacturer and regional company. Coordinates the flow of information between the individual groups of people involved in a project.
About this document 1 Applicable documents Conventions for text marking Markups Special markups are shown in this document as follows: ⊳ Requirement for a behavior instruction 1. 2.
1 About this document Download center 1.2 Download center You can download various types of documents, such as data sheets, installation instructions, and license texts via the following Internet address: https://siemens.com/bt/download l Enter the document ID in the search field. You will also find information about search variants and links to mobile applications (apps) for various systems on the home page. 1.
About this document Revision history 1 1.4 Revision history The reference document's version applies to all languages into which the reference document is translated. The first edition of a language version or a country variant may, for example, be version 'd' instead of 'a' if the reference document is already this version.
2 Safety Safety instructions 2 Safety 2.1 Safety instructions The safety notices must be observed in order to protect people and property. The safety notices in this document contain the following elements: ● Symbol for danger ● Signal word ● Nature and origin of the danger ● Consequences if the danger occurs ● Measures or prohibitions for danger avoidance Symbol for danger This is the symbol for danger. It warns of risks of injury. Follow all measures identified by this symbol to avoid injury or death.
Safety Safety regulations for the method of operation 2 How risk of injury is presented Information about the risk of injury is shown as follows: WARNING Nature and origin of the danger Consequences if the danger occurs ● Measures / prohibitions for danger avoidance How possible damage to property is presented Information about possible damage to property is shown as follows: NOTICE Nature and origin of the danger Consequences if the danger occurs ● Measures / prohibitions for danger avoidance 2.
2 Safety Safety regulations for the method of operation CAUTION Noncompliance with the following safety regulations Risk of injury to persons and damage to property ● Compliance with the following regulations is required. ● Specialist electrical engineering knowledge is required for installation. ● Only an expert is permitted to carry out installation work. Incorrect installation can take safety devices out of operation unbeknown to a layperson.
Safety 2 Standards and directives complied with Disregard of the safety regulations Before they are delivered, Siemens products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or the disregard of danger warnings contained in the documentation.
3 Structure and function Overview 3 Structure and function 3.1 Overview Figure 1: Line separator FDCL221 The line separator FDCL221 is an electronic switch which is mounted on a FDnet/C-NET detector line. The line separator detects short-circuits and open lines on the detector line and disconnects the negative conductor in the event of a short-circuit. The area of the detector line unaffected by the short-circuit can continue to be operated.
Structure and function Setup 3 Mounting ● ● Installation in intermediate distributor or directly in a fire control panel Attachment options: – Directly on a U-rail TS35 – Attachment with a screw or cable tie directly on a wall See also 2 Applicable documents [➙ 7] 2 Assembly [➙ 22] 3.1.1 Details for ordering Type Order number Designation FDCL221 A5Q00004011 Line separator 3.
3 Structure and function Function 3.3 Function The line separator FDCL221 is an electronic switch which is mounted on a FDnet/C-NET detector line. Station FDCL221 FDCL221-M Figure 3: Use of a line separator FDCL221 on a FDnet/C-NET detector line The line separator detects short-circuits and open lines on the detector line and disconnects the negative conductor in the event of a short-circuit. The area of the detector line unaffected by the short-circuit can continue to be operated. 3.3.
Structure and function Accessories 3 3.4 Accessories 3.4.1 U-rail TS35 ● ● ● ● ● ● Standard DIN rail for installing devices Width: 35 mm Length: 122 mm or 288 mm Compatible with: – Various input/output modules – Line separator FDCL221 – Mounting foot FDCM291 – Line adapter (Ex) FDCL221-Ex – Sounder module FCA2005-A1 – Fiber network module FN2006/FN2007 Order number (length 122 mm): BPZ:5644780001 Order number (length 288 mm): BPZ:5644230001 3.4.
4 Planning Accessories 4 Planning Unique detector line topology recognition is only ensured if at least one device with a separating function is present between two sub-stub lines. In this case a line separator. Station FDCL221 FDCL221-M Figure 4: Line separator FDCL221 between two sub-stubs If several sub-stub lines are to be activated on one FDnet/C-NET loop, failure of large numbers of devices must be prevented in the event of a line short-circuit.
Planning Accessories 4 Rules for the branching of a sub-stub from a loop ● ● Only one sub-stub is permitted between two FDnet/C-NET devices. One sub-stub is permitted at the start and end of the loop respectively, between the connection terminals of the fire control panel and the first line device. ● If there is more than one stub between two FDnet/C-NET devices, a line separator must be fitted between the stubs.
4 Planning Accessories Figure 6: Housing FDCL221 line separator in the control panel 1 Control panel C Sub-stub C 2 FDnet/C-NET loop D Sub-stub D 3 Line separator FDCL221 T FDnet/C-NET device A Sub-stub A X Terminal blocks or micro terminals B Sub-stub B You will find information on permissible topologies in fire detection systems FS20/FS720 in the 008843 (for 'Sinteso') and A6V10210362 (for 'Cerberus PRO') documents in the 'Line separation function' chapter.
Planning 4 Compatibility 4.1 Compatibility Compatible with control panels that support the FDnet/C-NET detector line. Detector line FC20xx FC72x FDnet X – X C-NET – X – 1 SIGMASYS AlgoRex 1 X – 1 FC360 – X With suitable line card X = compatible – = not compatible You will find detailed information in the 'List of compatibility'. 4.2 Fields of application The line separator is required in a FDnet/C-NET, where several sub-stub lines converge at one point.
5 Mounting / Installation Assembly 5 Mounting / Installation 5.1 Assembly The line separator may be fitted in any position. Ensure that the line separator LED is visible after mounting. You can fit the FDCL221 line separator in various ways: ● Directly on a U-rail TS35 ● With a cable tie on the mounting hole ● With a screw on the mounting hole Mounting on a U-rail TS35 1 Figure 7: Installing the line separator on a U-rail 1 Pair of terminal blocks l Mount the line separator to the U-rail.
Mounting / Installation 5 Installation Mounting with mounting hole 1 Figure 8: Mounting hole in FDCL221 1 Mounting hole with Ø 4.4 mm Use a screw to secure the line separator onto a plane surface or use a cable tie to secure to a grid. See also 2 U-rail TS35 [➙ 17] 5.2 Installation ● Specialist electrical engineering knowledge is required for installation. ● Only an expert is permitted to carry out installation work.
5 Mounting / Installation Installation 5.2.1 Wiring w Always insert a line separator before a sub-stub line. 1. Connect the line separator to the FDnet/C-NET. The pigtails are provided with pressed-on 2.8 x 0.8 mm flat connector sleeves in the factory. Cut off the flat connector sleeves if you don't need them for the connection. 2. Connect a sub-stub line to the same terminal on the FDnet/C-NET. The following diagram shows one possible mounting variant where the individual components are wired.
Mounting / Installation Installation 5 5.2.2 Shielded cable Shielded cables must be earthed in stars at one point (e.g. on the control panel). Cable shieldings must be linked with one another using an insulated micro terminal or connection terminal. The shielding must not touch any extrinsic earthing potentials or metal parts in the device.
6 Commissioning 6 Commissioning The devices are commissioned via the control panel. The exact procedure is described in the control panel documentation. Conduct a performance check once commissioning is complete.
Maintenance and troubleshooting 7 7 Maintenance and troubleshooting The line separator module is maintenance-free. It monitors itself and has to be replaced if damaged.
8 Specifications Technical data 8 Specifications 8.
Specifications Technical data Ambient conditions Operating temperature 8 -25…+70 °C Operating temperature tested according to -10…+55 °C EN 54-17 Mechanical data Storage temperature -30…+80 °C Air humidity (non-condensing) ≤95 % rel. Protection category (IEC 60529) IP44 Dimensions (L x W x H) 47.5 x 44 x 10 mm Weight 0.
8 Specifications Dimensions 8.2 Dimensions 10 47.5 44 4.4 1 Figure 11: Dimensions of FDCL221 line separator 1 Pigtail 0.5 mm2, length = 500 mm, with 2.8 x 0.8 mm flat connector sleeve pressed on in the factory 8.3 Environmental compatibility and disposal This equipment is manufactured using materials and procedures which comply with current environmental protection standards as best as possible.
Index Index Application area Ambient conditions.......................................... 21 Approvals ....................................................... 28 Attachment Cable tie ......................................................... 15 Screw ............................................................. 15 U-rail............................................................... 15 Chemicals....................................................... 21 Moisture .............................................