Data Sheet for Product
6
Smart Infrastructure A6V11712831_de--_c
2021-01-25
Technical data
Supply
Operating voltage ● DC12...33V for FDS364‑x
● DC16...33V for FDS366‑xx
Operating current (quiescent) ● 250µA for FDS364‑x
● 400µA for FDS366‑xx
● Tone activated
1
Max.4mA (128mW)
● Beacon activated
2
LED white Medium (W‑2.4‑7.5): 13mA (208mW)
Indicator: 3mA (48mW)
LED red Medium (W‑2.4‑7.5): 17mA (272mW)
Indicator: 3mA (48mW)
● Beacon and tone activated
12
LED white Medium (W‑2.4‑7.5): 16mA (296mW)
Indicator: 5mA (160mW)
LED red Medium (W‑2.4‑7.5): 20mA (360mW)
Indicator: 5mA (160mW)
1
Max. sound level for tone is taken into account
2
Only with FDS366-xx
Functional data
Tones ● 16tones (including school bell)
● 2alarm levels ('Warning' and 'Evacuation')
● 1sound level (maximum)
Sound level (alarm sound level) FDS364‑x, FDS366‑xx: 75…99dBA
Luminous intensity
1
(according to EN54‑23)
LED white Medium (W‑2.4‑7.5)
Indicator: 0.4…5cd
2
LED red Medium (W‑2.4‑7.5)
Indicator: 0.3…3cd
2
Luminous intensity levels
1
2levels (medium/indicator)
Communication protocol C‑NET
C‑NET system compatibility FC360
Color ~RAL9010pure whiteor
~RAL3000flame red
1
Only with FDS366-xx
2
Does not comply with EN54-23
Line connections
Conductor cross section 0.2...2.5mm
2