Installation Instructions

2
Figure 3
Mounting Information
using the cable provided with the Programmer/
Tester.
NOTE: The connection from the FPI-32 to the
MSI-30B/-51BD is not polarity sensitive. However,
connection from the Control Panel to the MSI-30B/
-51BD is polarity sensitive.
3. Following the instructions given in the FPI-32
Programmer/Tester Manual (P/N 315-090077),
program the MSI-51BD to the desired address. To
program the MSI-30B, follow the instructions on
page 3.
4. Record the device address on the label located on
the MSI-30B/-51BD housing. (See Figure 1.)
5. Distribute the manual station boxes throughout the
protected area so that they are unobstructed, readily
acessible, and located in the normal exit path.
6. Place the manual station according to the regulations
of the authorities having jurisdiction.
For surface mounting, mount the backplate of the
MSI-30B/-51BD to a Model MC-5 Backbox. (Refer to
Figure 3.)
For flush mounting, mount the backplate to a user-
supplied single gang switchbox.
CAUTION: Do not overtighten the screws. Over-
tightening may distort the backplate.
7. Install the MSI-30B/-51BD. (Refer to Figure 3.)
8. Wire the MSI-30B/-51BD to the System. (Refer to
Figure 2 for proper connections.)
9. In supervisory: MSI-30B/-51BD draws 1mA.
MSI-30B Mounting
MSI-51BD Mounting