Data Sheet for Product
s Canada Limited 
Mounting Diagrams 
Wiring Diagrams 
Notes: 
1. Recommended wire sizes: 
  18 AWG minimum, 14 AWG maximum 
2. Wire larger than 14 AWG can damage the connector. 
3. When using shielded cable without metal raceway or with 
nonmetallic raceway, the shields should be terminated at the 
device ground terminal. If the device box is already grounded 
by another means
 ─ such as being mounted to a grounded 
structure 
─ then the wire shields should be continuous, and 
must be grounded solely at the point of origin. 
[For example, at the control panel, the device ground terminal shall 
 be connected to the grounded device box.] 
4. When using shielded cable with metal raceway, the wiring shields 
shall be continuous and grounded solely at the point of origin. The 
device ground terminal shall be connected to the grounded device box. 
5. When using metal raceway without shielded cable, connect the 
device ground terminal to the grounded device box. 
6. Metal raceway should be continuously grounded throughout 
the system. 
Details for Ordering 
Model 
Number 
Part 
Number 
Description 
MSI-30BC 
500-693376 
Intelligent Manual Station  
(Two-stage, dual-address Intelligent Manual Station 
used with NC auxiliary contacts) 
MSI-51BD 
500-033480 
Intelligent Manual Station 
(Single-address station used with NC auxiliary contacts) 
MSI-30BC
MSI-51BD
MSI-30BC
MSI-51BD