Installation Instructions
P/N 315-033450FA-4 PAGE 1 OF 2
INTRODUCTION
The Model 8700-M Manual Station is an addressable device containing advanced control
panel communication technology. This technology, which provides two-direction commu-
nication with the control panel, produces an Intelligent Initiating Device. The 8700-M is a
single action station; when used with the Model F451173 Adapter, the 8700-M is double
action.
PROGRAMMING INSTRUCTIONS
IMPORTANT NOTE: The 8700-M must be in the Reset position in order for the
unit to be programmed. If the pull-down lever has been even partially pulled
down, the unit must be reset before it can be programmed.
1. Refer to Figure 1 to locate the opening on the 8700-M cover that allows access to the programming
holes which are on the 8700-M printed circuit board.
2. The manual station is programmed by using the 8720 Programmer/Tester. Because 8700-M devices
are polarity insensitve, the programming plugcan be inserted into the programming holes in either
direction.
To prevent potential damage to the 8720 DO NOT connect an 8700-M to the 8720 until at least one wire
is removed from terminals 1 or 2 of the 8700-M.
3. Follow the instructions in the 8720 Manual (P/N 315-033260FA) to program the 8700-M to the desired
address. Record the device address on the nameplate label located on the inside of the 8700-M
manual station mounting plate. The 8700-M can now be installed and wired to the system.
OPERATION
The 8700-M manual station operates with the Fire Alarm Control Panel via the addressble device circuit.
When an alarm condition occurs, pull down on the PULL DOWN lever of the manual station. The pull-
down cover remains down and locked until the station is reset.
The 8700-M with the F451173 Adapter has an additional lever labeled LIFT - PULL HANDLE which must
be lifted up before access is provided to the station PULL DOWN lever.
To Reset Station
Turn lock barrel ΒΌ turn counter-clockwise with the allen key provided. This will allow the front to hinge
down, releasing PULL-DOWN plate to disengage from the switch.
Return the front to its closed position, then turn the lock barrel back clockwise.
Figure 1
8700-M Cover
OPENING TO
PROGRAMMING
POINTS
INSTALLATION INSTRUCTIONS AND WIRING FOR
ADDRESSABLE METAL MANUAL PULL STATION
P/N 8700-M
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ