Installation Instructions
Air Duct Monitoring Housing
Installation Instructions
Model AD2-4W
INTRODUCTION Model AD2-4W from Siemens Industry, Inc., is an air duct
monitoring housing containing sampling tubes. When used
with a PE-11 smoke detector, smoke and combustion
products are detected for shutdown of the duct system and/
or operation of supplementary equipment as provided by the
system control panel. The duct unit supports two sets of
Form C alarm contacts, one Form A alarm contact and one
Form C trouble contact. The trouble contact supervises the
presence of the input power, removal of the detector cover
and the removal of the smoke detector head.
TECHNICAL DATA AIR DUCT CONDITIONS
Temperature Range:
32
O
F (0
O
C) - 100
O
F (38
O
C) per UL 268A
Altitude Range:
No altitude limitations
Relative Humidity:
Up to 85% RH (non-condensing/non-freezing)
Air Duct Velocity Range:
100-4000 ft/min
Sampling and Exhaust Tube Pressure Differential Range:
Greater than 0.01 and less than 1.2 inches of water column
These air duct detectors are designed for detection and
control of products of combustion in a duct system. They are
not to be used as a substitution for open area protection.
DO NOT USE air duct detectors with Alarm Verification.
ASSEMBLY This detector has a cover tamper (removal) switch. Care
should be taken when installing the cover. Squarely place the
cover on the unit to aviod possible damage to the switch.
DO NOT SLIDE COVER INTO POSITION.
Siemens Industry, Inc.
Building Technologies Division
P/N 315-049709-3
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ P/N 315-049709-3
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada
ELECTRICAL RATINGS FOR PE-11
REMOTE ACCESSORIES
SEIROSSECCAETOMER
TOLIP
DEL
)neerG(
MRALA
DEL
)deR(
ELBUORT
DEL
)wolleY(
NROH
SGNITARLACIRTCELE
LEDOMNOITPIRCSED
YBDNATSMRALAELBUORT
R/P/AK-SM
detarepo-yek,toliP,mralAetomeR
hctiwSteseR/tseT
••
Am51Am53Am0
P/AR-SMtoliP,mralAetomeR
••
Am51Am53Am0
T/A/P/AK/HR-SM
,nroH,toliP,elbuorT,mralAetomeR
hctiwSteseR/tseTdetarepo-yek
••••
Am51Am55Am51
R/R001-RSM
/ylbmessAlortnoC/rotacidnIetomeR
etalprevoCgnaGelgniSdeR
Am51Am05Am55
W/R001-RSM
/ylbme
ssAlortnoC/rotacidnIetomeR
etalprevoCgnaGelgniSetihW
Am51Am05Am55
SAGTSETEKOMS
11-GTsaGtseTrotceteD
NGT-DAtiKe
lzzoNsaGtseT
DAEHROTCETEDEKOMS
051490-005rotceteDcirtceleotohP11-EP
If the fire alarm system is connected to a central station or fire
department, or operates external devices such as fans, extin-
guishers, etc., connected, notify appropriate personnel and
disconnect the external devices until all tests are completed.
After testing, reset the system, reconnect the devices, and notify
the personnel that the system is operating again.
ELECTRICAL RATINGS FOR AD2-4W
TUPNI
TNERRUC
YBDNATS
TNERRUC
)lacipyT(
MRALA
TNERRUC
)lacipyT(
ELBUORT
TNERRUC
)lacipyT(
CDV42Am92Am321Am02
zH06@CA
V42Am08Am372Am56
zH06@CAV511Am62Am75Am53
zH06@CAV032Am03Am83Am02
egatloVCDV72-61
elppiRkaep-ot-kaepV3
tnerruCyrosivrepuS.xamAu011
emiTpu-tratS.xamsdnoces05
tnerruCmralAAm05-33
The accessories available for use with AD2-4W are: