Installation Instructions

P/N 315-094926-4
Installation Instructions
Models RSAC-11 and RSAW-11
Remote Sensitivity and Alarm Indicators
Fire Safety
INTRODUCTION
The SIEMENS Models RSAC-11 (round plate) and
RSAW-11 (rectangular plate) Remote Sensitivity
and Alarm indicators work with a PE-11 detector.
The LED on the remote indicators mimics the color
of the LED on the detector. Use the remote indica-
tors in applications where the detector is not easily
viewed, such as air ducts and drop ceilings.
Each PE-11 detector can drive one RSAC-11 or
RSAW-11; however, the total number of detectors
and remote indicators must not exceed 30 devices
on an initiating zone. For example, each zone may
have 29 PE-11s and 1 RSAC-11, or 15 PE-11s and
15 RSAW-11s.
The RSAC-11 or RSAW-11 contains an LED
indicator that flashes in one of three colors: green,
yellow, or red. When the PE-11 detector flashes,
the remote indicator flashes in the same color. The
flashes occur approximately every 7 seconds and
are described in Table 1.
TABLE 1
LED Status Indicates
Green Normal supervisory operation.
Smoke sensitivity within rated
limits.
Yellow Detector requires service (cleaning
or repair) or is operating beyond its
environmental specifications.
Red Alarm condition. LED flashes
every 2.5 seconds
No flash Detector or RSA-11 is not powered
or requires repair.
INSTALLATION
The remote indicator may be placed up to 25 feet away
from its associated detector using 14-18 gauge wire.
1. Use a single-gang switch box (user supplied) for
mounting the RSAW-11; Use a 4 inch octagonal
conduit box (use supplied) for mounting the
RSAC-11.
2. a. When connecting to the RR-11 remote relay,
make the connections to the relay base TB2
(See the RR-11 Installation Instructions,
P/N 315-094924).
b. When no connection to the RR-11 remote relay
is made, route the wires through the hole in the
detector base and make the connection to the
screw terminals on the on the PE-11. Refer to
Figure 1.
Figure 1
RSA-11 Connection Diagram
Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
Siemens Building Technologies, Ltd.
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 CN