User Manual

Mounting
Laying the cables and connecting the batteries
4
18 | 32 A6V10393194_e_en_--
The following instructions must be observed.
The cable cross section for each of the three lines of the mains cable is
1.5…2.5 mm
2
.
The mains cable must be inserted from above on the left of the housing and
must not be laid outside the boundary of the mains zone.
The lines of the mains cable must be secured with a cable tie.
Signal lines must only be fed into the housing on the right from above or from
the rear.
Signal lines must be secured with a cable tie.
Cable entries must be closed completely.
No cable entries should be made in the back box.
Batteries must be installed so that they cannot leak.