Data Sheet for Product

Siemens Data Sheet 9806
Smart Infrastructure Building Products usa.siemens.com/fire
Product Overview
The 170-Watt power supply (Model FP2011-U1) and 300-Watt power supply (Model
FP2012-U1) provide primary, regulated (24VDC, nominal) power for normal operation
to Siemens Fire Safety systems. Both power supplies are filtered and regulated.
Model FP2011-U1 is rated 24VDC, nominal, at 6.5 Amps, and Model FP2012-U1 is
rated 24VDC, nominal, at 11.5 Amps.
Notes: Model FP2011-U1 is used with Models FC901, FC922 and FC924 FACPs.
Model FP2012-U1 operates with Models FC922 and FC924 FACPs, as well
as with Models FV922 and FV924 IVC panels.
The 170-Watt power supply incorporates a 4.0A, non-resettable slow-blow fuse on the
primary input, and includes a built-in AC-line filter for surge and noise suppression.
Model FP2011-U1 mounts in a standard Cerberus PRO-brand enclosure, and there are
no serviceable parts to be maintained.
The 300-Watt power supply incorporates two (2) 6.3A replaceable, non-resettable
slow-blow fuses on the primary input and includes a built-in AC line filter for surge and
noise suppression. Model FP2012-U1 mounts in a Cerberus PRO-brand enclosure, and
there are no serviceable parts to be maintained.
Both power supplies are FM (#3010); FDNY (#6104) and CSFM (#7165-0067:0259)
Approved.
Cerberus® PRO
170-Watt and 300-Watt Power Supplies
Models FP2011-U1 I FP2012-U1
Architect & Engineer Specifications
170W (Model FP2011-U1) and 300W
(Model FP2012-U1) output power to
fire-only and intelligent voice
communication (IVC) systems
Model FP2011-U1 used with
various Siemens fire-alarm
control panels (FACPs)
Up to 252 | 504-point
addressable FACPs or IVC
panels can obtain primary,
regulated power from 300W
power supplies, Model
FP2012-U1
Operates with 120VAC or 240VAC
Monitors AC-power failure and
‘brownout’ conditions
Short-circuit or over-current
protection
UL-recognized component
UL 864 10th Edition / UL 1481 and
ULC-S527 Listed
FM, CSFM and NYC Fire Department
Approved
Model
FP2012-U1
Model
FP2011-U1