FP2015-A1 Power supply (70 W) Technical Manual A6V10411051_d_en_-2020-01-20 Smart Infrastructure
Imprint Imprint Technical specifications and availability subject to change without notice. Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders will be held liable for payment of damages. All rights created by patent grant or registration of a utility model or design patent are reserved. Issued by: Siemens Switzerland Ltd.
Table of contents A6V10411051_d_en_-- 1 About this document................................................................................. 5 1.1 Applicable documents .............................................................................. 7 1.2 Download center....................................................................................... 7 1.3 Revision history ........................................................................................ 7 2 Safety ..................
| 20 A6V10411051_d_en_--
About this document 1 1 About this document Goal and purpose This manual describes the design and functions, as well as the key work steps required for mounting and installation. Information about the function check, maintenance, and troubleshooting makes it possible to use the product as intended. Scope The information contained in this document is valid for FP2015-A1 power supply (70 W).
1 About this document Document identification The document ID is structured as follows: ID code Examples ID_ModificationIndex_Language_COUNTRY -- = multilingual or international A6V10215123_a_de_DE A6V10215123_a_en_-A6V10315123_a_--_-- Date format The date format in the document corresponds to the recommendation of international standard ISO 8601 (format YYYY-MM-DD).
About this document Applicable documents 1 1.
2 Safety Safety notes 2 Safety 2.1 Safety notes Comply with the following safety notes to protect life, limb, and property. The safety notes in the document include the following elements: ● Symbol for hazard ● Signal word ● Type and source of hazard ● Consequences in the event the hazard occurs ● Measures or prohibitions to prevent the hazard Symbol for hazard This is the symbol for hazard. It warns you of Risks of injury. Comply with all measures designated by this symbol to prevent injury or death.
Safety Safety regulations for the method of operation 2 DEPICTION for possible damage to property Notes on possible damage to property is depicted as follows: NOTICE Type and source of hazard Consequences in the event the hazard occurs ● Measures/prohibitions to prevent the hazard 2.2 Safety regulations for the method of operation National standards, regulations and legislation Siemens products are developed and produced in compliance with the relevant European and international safety standards.
2 Safety Standards and directives complied with Testing the product operability ● ● ● ● ● ● Prevent the remote transmission from triggering erroneously. If testing building installations or activating devices from third-party companies, you must collaborate with the people appointed. The activation of fire control installations for test purposes must not cause injury to anyone or damage to the building installations.
Safety 2 Standards and directives complied with WARNING Limited or non-existent fire detection Personal injury and damage to property in the event of a fire. ● Read the 'Release Notes' before you plan and/or configure a fire detection installation. ● Read the 'Release Notes' before you carry out a firmware update to a fire detection installation. NOTICE Incorrect planning and/or configuration Important standards and specifications are not satisfied.
3 Description 3 Description ● ● ● ● ● ● ● The power supply (70 W) converts mains voltage to system voltage and charges the batteries. The DC 24 V system voltage is electrically isolated. For the supply of consumers in accordance with EN 54-4 and VdS. The output voltage is short-circuit-proof and battery charging is current-limited. Must not be connected in parallel. The battery charge voltage is regulated with temperature compensation.
Structure and function Views 4 4 Structure and function 4.1 Views X1 X2 F1 F3 Figure 1: View of PCB FP2015-A1 power supply (70 W) Designation Position Function Connector X1 Mains connection X2 Output for battery supply and signal lines F1 Mains fuse 3.15 A/T AC 250 V; 5 x 20 mm F3 Battery fuse 3.
4 Structure and function Pin assignments 4.2 Pin assignments 4.2.1 X1 mains connection Pin Designation 1 Description Ground (protective conductor PE) 2 N Neutral conductor 3 L External conductor (L1) Admissible cable cross-section: 0.2…2.5 mm² 4.2.
Switching the mains voltage to AC 115 V 5 5 Switching the mains voltage to AC 115 V The mains voltage set in the factory is AC 230 V. 1. Open the power supply housing. 2. Switch the jumper from position X12 = AC 230 V to position X11 = AC 115 V. Jumper X12 = AC 230 V Jumper X11 = AC 115 V 3. Mark the change from AC 230 V to AC 115 V on the product label as shown below. s Power supply (70 W) Typ : FP2015-A1 P.Nr.
6 Technical data 6 Technical data Mains supply System supply output Voltage AC 97…127 V, AC 196…253 V, 50 / 60 Hz Current 0.5…1 A Power consumption Max. 90 VA Designation 'Usys' Voltage DC 20.5…28.6 V, depending on charge and temperature Current: ● Maximum output current with battery charge (Imax a) 0.9 A ● Maximum output current without battery charge (Imax b) 2.5 A ● Minimum output current (Imin) 0.05 A Output power 70 W Ripple Max. 5 % Designation 'Accu' Voltage DC 20.5…28.
Technical data Approvals A6V10411051_d_en_-- VdS G213083 LPCB 126, 531 6 17 | 20
7 Disposal 7 Disposal The device is considered an electronics device for disposal in terms of European Directive 2012/19/EU and may not be disposed of as domestic garbage. ● Dispose of the device through channels provided for this purpose. ● Comply with all local and currently applicable laws and regulations.
A6V10411051_d_en_-- 19 | 20
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies A6V10411051_d_en_-- © Siemens Switzerland Ltd, 2014 Technical specifications and availability subject to change without notice.