FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual P/N 315-049353-1 Technical Manuals Online! - http://www.tech-man.
Technical Manuals Online! - http://www.tech-man.
TABLE OF CONTENTS INTRODUCTION.................................................................................................................. 1 CONTROL PANEL LIMITATIONS .................................................................................... 1 PREFACE......................................................................................................................... 2 DESCRIPTIONS ............................................................................................................
CONTROL PANEL OPERATION ...................................................................................... 12 OPERATION INSTRUCTIONS ....................................................................................... 12 Standby Condition ...................................................................................................................................... 12 Alarm Conditions ...............................................................................................................
P2 Addressable Device Circuit(s) .............................................................................................................. 35 P2 Addressable Device Wiring Diagrams.................................................................................................. 36 PROGRAMMING THE CONTROL PANEL ....................................................................... 38 KEYPAD PROGRAMMING ............................................................................................
iv Technical Manuals Online! - http://www.tech-man.
FS-250 Installation and Operation Manual INTRODUCTION CONTROL PANEL LIMITATIONS This control panel may not show an alarm condition without compatible initiating devices (smoke detectors, etc.) and notification devices (horn, lights, etc.) connected to it. Electrical ratings of the initiation and notification appliances must be compatible with the electrical ratings of the control panel and must be properly interconnected.
FS-250 Installation and Operation Manual PREFACE Along with the use of this instruction manual, the appropriate following standards and the manufacturer's instructions for initiating and notification devices should be used to install and maintain a functioning fire alarm signaling system. NFPA 70 National Electrical Code NFPA 72 National Fire Alarm Code NFPA 101 Life Safety Code For other standards that may apply contact the authority having jurisdiction.
FS-250 Installation and Operation Manual DESCRIPTIONS FS-250 SYSTEM DESCRIPTION The FS-250 is a modular fire alarm control panel. It features advanced addressable detection, programming, and memory capability. Its base configuration includes a power supply, a P2 addressable device circuit, four/ two notification circuits (NAC), serial interface circuit, four-status relays, and a programming port. The FS-250 control panel mounts in a 22" x 18" back-box with overall cover size of 229/32" x 18-3/8".
FS-250 Installation and Operation Manual P2 Addressable Device Circuit The FS-250 control panel has one addressable device circuit utilizing the P2 Detection Technology. The circuit has the capacity for 252 addresses. Notification Appliance Circuits The FS-250 control panel has four independent Class B (Style Y) notification appliance circuits (NACs). Pairs of NACs can be combined for Class A (Style Z) operation. This reduces the number of NACs to two.
FS-250 Installation and Operation Manual Battery Sets The FS-250 control panel is designed to use only sealed lead-acid or equivalent batteries for back-up power. Attaching a close-coupled battery box, if required, may allow use of battery sets beyond the physical capacity of the enclosure (12 AH for the FS-250). Maximum battery charging capacity for the FS-250 is 38.5 AH.
FS-250 Installation and Operation Manual outputs. It can also be programmed to silence Siemens sync horns while the sync strobes remain on, using two wires. This requires a silenceable and non-silenceable input. The PAD-3 also offers a 3 amp auxiliary output for driving other portions of your fire alarm system. P2 ADDRESSABLE DEVICES FirePrint™ Smoke Detector The control panel processor sends the sensitivity and pre-alarm settings to the detectors and polls the detectors as to their status.
FS-250 Installation and Operation Manual EVENT HISTORY The control panel includes a non-volatile memory recording up to 2000 system events. Identified alarm, trouble, supervisory trouble, and other significant events will be recorded along with the date and time of occurrence, and can be inspected by operating front panel push buttons. Events recorded in the history are: • • • • • • • • • • • • • • • • • • • • • • • • • • • • Alarm, Trouble, or Supervisory conditions. Drill, Recall and General Evacuation.
FS-250 Installation and Operation Manual GENERAL DESIGN FEATURES Environmental All hardware is suitable for use in an interior or protected location. Power Limiting The AC power and battery wiring are not power limited. All other circuits leaving the control panel are power limited, provided the proper installation rules are maintained. Ground Fault Detection The control panel provides system ground fault detection and a ground fault will trigger the common fault buzzer and system trouble LED.
FS-250 Installation and Operation Manual Serial Interface Circuit responds to an address poll. If a configured device is missing, the system reports a trouble. The system also polls unused addresses periodically. If a device responds to such a poll of a non-configured device, the system reports a trouble. Two devices addressed the same also cause a trouble to be reported. REGULATORY STANDARDS The FS-250 control panel meets the requirements of industry and government regulatory agencies as noted.
FS-250 Installation and Operation Manual • Voltage: 24 VDC nominal Ripple: 1.5 VAC maximum Resettable Power Output Power limited Voltage: 24 VDC nominal Ripple: 1.5 VAC maximum Status Relays Four relays programmable for alarm, supervisory, trouble, loss of AC. • Contact Rating: 1 A, 28 VDC maximum, resistive • Form C Contact Notification Appliance Circuits • Power limited • Supervised • Maximum Standby Current: 3.
FS-250 Installation and Operation Manual Municipal Tie (Optional Municipal Tie Board FS-MT) CA • Reverse Polarity: Selectable for Alarm with Trouble or Alarm only operation • Power limited • Supervised by receiver for short or open circuit. • Supervised by control panel for grounded circuit. • Voltage: 24 VDC nominal • Current: 0.020A maximum (normal or trouble) • Current: 0.025A maximum (shorted) • Ripple: 1.
FS-250 Installation and Operation Manual CONTROL PANEL OPERATION OPERATION INSTRUCTIONS Standby Condition In normal standby operation, the green AC POWER ON LED should be illuminated and no other indicator operating. The display will show the system name, “System Normal” announcement and the current date, day, and time. Alarm Conditions • NORMAL ALARM In case of alarm, the system alarm LED will operate in a flashing mode and the buzzer will sound.
FS-250 Installation and Operation Manual • PRE-SIGNAL A point activated by a PRE-SIGNAL alarm device activates the alarm relay, alarm DACT, alarm LEDs and buzzers, and all user programmed outputs normally, except NACs. Only pre-signal NAC(s) operate at this time. Pre-signal NACs are for constantly attended central locations manned by trained building personal.
FS-250 Installation and Operation Manual Supervisory Conditions Supervisory troubles are indicated similar to regular system troubles except that when a supervisory trouble is cleared, the cleared condition continues to be indicated until it is acknowledged. Maintenance In order to insure continued safe and reliable operation of the fire alarm system, periodic inspection and testing should be performed in accordance with applicable NFPA 72 standards.
FS-250 Installation and Operation Manual Recall To signal recall after a drill, proceed as follows: • • • • • Press "MENU". At the next screen, select "More". Select "RECALL". At the next screen, select "Yes". Operate ALARM SILENCE to terminate recall signal. Pre-Alarm • A pre-alarm condition is annunciated by Pre-alarm LEDs and buzzers on the control panel and LCD Annunciators and Remote Processors. The LEDs flash and buzzers are on steady until acknowledgment.
FS-250 Installation and Operation Manual History The last 2000 system events are time-tagged and recorded for review in the user level event history. This history is available to anyone with the door key, but may be erased only at the maintenance security level. • Operation of history: New events overwrite old when filled. Printer (if used) records all events. For more information see the event history section • Access to history: To recall past events, proceed as follows: Press MENU button.
FS-250 Installation and Operation Manual FS-250 OPERATING INSTRUCTIONS Alarm Operation In case of alarm, the System Alarm LED flashes, LCD will display alarm conditions and the panel buzzer sounds. Local audible and visual signals and remote alarm signals operate. When an alarm occurs, proceed according to the established emergency plan.
FS-250 Installation and Operation Manual FS-RD2 OPERATING INSTRUCTIONS Alarm Operation In case of alarm, the System Alarm LED flashes, LCD will display alarm conditions and the buzzer sounds. Local audible and visual signals and remote alarm signals operate. When an alarm occurs, proceed according to the established emergency plan.
FS-250 Installation and Operation Manual CONTROL PANEL INSTALLATION PARTS SUPPLIED – FS-250 With Enclosure Packages (Black or Red) Backbox Assembly Front Door Assembly with Window Inner Door Assembly With Electronics Package FS-MB Main Board FS-DB Display Board FS-DLC Loop Driver Board 215-649112 Keyboard 330-944373 Thermal pad 465-633943 Battery cable assembly 315-048353 Owner’s Manual 575-249351 Riser Diagram 315-049352 Operating Instructions 600-149373 Ground Wire Assembly 899-G67197 #6-32 Keps Nuts (1
FS-250 Installation and Operation Manual INSTALLATION The enclosures must be fastened securely to a clean, dry, shock-free, and vibration-free surface. Consider the following when mounting the box. Mounting height for visual and manual access to the Display Board Weight and size of backbox Local mounting codes When mounting the backbox, position the backbox clear of obstructions so that the door can open freely and so that indicators and controls are easily accessible.
FS-250 Installation and Operation Manual • • • • • Place the backbox over the two top bolts and allow it to slide down over the bolts. Mark, drill, and install the two bottom bolts in the backbox. Tighten all four bolts securely against the back wall of the backbox. The PAD-3 Auxiliary Power Supply or battery enclosure may be mounted immediately below the main enclosure, close nipple, allowing a minimum of 1 inch in between the enclosures for clearance between the doors.
FS-250 Installation and Operation Manual Remove Knock-Outs Prepare the enclosure for electrical wiring, break out the appropriate conduit entry points. Segregation is required between power limited and non-power limited conductors. In order to maintain the minimum separation, the following wire routing is illustrated. Separation of at least a 1/4 inch is required between the non-power limited and power limited conductors. Power limited and non-power limited wiring must be run in separate conduit.
FS-250 Installation and Operation Manual Transformer Mounting – FS-NPE • Place the two FS-NPE transformer assemblies over the bottom two sets of studs on the left side of the enclosure. Mounting the transformer can be accomplished before mounting the enclosure if desired. • Tighten provided transformer-mounting nuts. • Plug the transformer assemblies into connectors J1 and J2 on the Main Board. Bottom transformer plugs into J1.
FS-250 Installation and Operation Manual FS-DLC Loop Driver Board Mounting • Place the four provided standoffs in locations shown on the Main Board. • Carefully align connector J1 on the Loop Driver Board with connector J9 on the FS-250 Main Board. Standoffs FS-DLC Loop Driver Board FS-250 Door Assembly • Secure the Lexan window to door assembly using four of the provided #6-32 keps nuts. • Place the Door Assembly on Backbox using five of the provided #6-32 keps nuts.
FS-250 Installation and Operation Manual Display Board Installation • With the Inner Front Plate closed, carefuly pass connector and cable from keypad through vertical slot in front plate. • Remove backing from keypad and carefully attach keypad to front plate. Center window in keypad on large opening in front plate. • Attach the cable connection from keypad on the Inner Front Plate to connector J3 on the Display Board (FS-DB).
FS-250 Installation and Operation Manual Front Plate Mounting • Secure the Front Plate Assembly to Door hinge using three of the provided #6-32 keps nuts. • Plug the Cable Assembly into connector J1 of the Display Board and to connector J11 of the Main Board. • Front Plate is secured in place when closed by the two provided #8-32 x 3/8 sems screws. Locations on the Front Plate for the sems screws are the upper and lower right corners when closed. 26 Technical Manuals Online! - http://www.tech-man.
FS-250 Installation and Operation Manual Ground Wire Installation – P/N 600-149373 • Attach Ground Wire (P/N 600-149373) to inside of outer door using provided #6 nut (P/N 950-220604). • Attach Ground Wire (P/N 600-149373) to outside of inner door using provided #6 screw (P/N 906-220604). SYSTEM WIRING Before connecting the field wiring, check the wiring for opens, shorts, grounds and stray voltages.
FS-250 Installation and Operation Manual Observe the wiring order -- the bottom terminal is ground and must be wired back to the electrical panel ground (earth) bonding point or another good ground acceptable to the authority having jurisdiction and the electrical inspector. The neutral wire must be taken back to the electrical panel neutral distribution bar and must not be grounded.
FS-250 Installation and Operation Manual Devices that may be satisfactorily used with the control panel are shown in the compatible device listing in Appendix B. Wire reference data are included in Appendix A.
FS-250 Installation and Operation Manual The overall arrangement of boards in the control panel is shown in the following diagram. Wiring Separation All high voltage and non-power limited wiring must be kept separate from power limited wiring. A separation of at least a 1/4 inch must be maintained, with high voltage and nonpower limited wiring running in separate conduit openings from power limited wiring.
FS-250 Installation and Operation Manual Primary And Secondary Power Wiring The AC main connections (TB1) and the battery connections (J4) must be made along the left-hand side of the main termination board. Route all high voltage and non-power limited wiring together and away from power limited wiring. TX-1 Supervised 120 VAC 60Hz 2.4A Max FS-250 Non-Power Limited AC AC N N GND GND B- B+ BAT.
FS-250 Installation and Operation Manual Status Relays And Auxiliary Power Outputs Wiring The right side of the main board provides for connection of status relay contacts and auxiliary power connections (TB5-8). Four relays with dry contacts are provided. These contacts can be dedicated to power fail, alarm, trouble and supervisory indications. The relay contacts are Form C and are rated 1A @ 28VDC resistive.
FS-250 Installation and Operation Manual Auxiliary Power Supply *Connect a PAD-3 auxiliary supply when power requirement calculation indicates that an additional source is required. For further information, refer to Appendix D. Battery Size Calculations For calculation of battery size requirements see Appendix A. NAC Wiring At the lower right corner of the main board are the terminal blocks (TB12, TB13) are used for the connection of notification appliances.
FS-250 Installation and Operation Manual Serial Interface Circuit The serial interface circuit can address up to 16 standard annunciators and/or 8 remote processors to drive graphic annunciation or relay modules. Devices on the circuit may be connected up to 4000 feet from the control panel. At the top of the main board, the terminal blocks are used for the connection of remote serial devices. Serial Interface Circuit, (=, -) 24VDC nominal, 0.
FS-250 Installation and Operation Manual Serial Remote Device Wiring Overview When connecting devices on the Serial Interface Circuit, the data wires must be daisy chained and with no T-taps to preserve the integrity of the data. Each end (two places) must be terminated with a 120 ohm termination resistor. The following diagrams show the proper wiring.
FS-250 Installation and Operation Manual P2 Addressable Device Wiring Diagrams Refer to the instruction sheets packed with each device. Detectors and modules may be wired together according to several NFPA defined wiring styles. The wiring style that is appropriate for your installation should be determined from the relevant building codes and the Authority Having Jurisdiction. Style 4 wiring permits branching of circuit connections.
FS-250 Installation and Operation Manual P2 ADDRESSABLE DEVICE CIRCUIT WIRING / OPERATION COMPARABLE TO NFPA STYLE 6 Style 6 provides redundant communication paths. . Siemens P2 Devices: Detectors, Monitor Modules, or Control Modules up to a maximum of 252 devices per addressable device circuit. A Maximum of 20 devices recommended between Isolator Modules. A Maximum of 15 Isolator Modules per addressable device circuit. 37 Technical Manuals Online! - http://www.tech-man.
FS-250 Installation and Operation Manual PROGRAMMING THE CONTROL PANEL KEYPAD PROGRAMMING Customized programming of the control panel may be accomplished through a keypad included in the control panel See the Siemens FS-250 Programmer’s Manual, P/N 315049403, for detailed information of system programming. PC PROGRAMMING Programming the panel may also be done by a temporary connection to the programming port with a computer.
FS-250 Installation and Operation Manual MAINTENANCE GENERAL Device sensitivity may be read out and alarm thresholds controlled on a per-point basis, as well as setting overall percent obscuration and day/night variations. Individual points may also be disabled for service. To perform these functions on the unit, enter the 4-digit maintenance password into the control panel or LCD annunciator.
FS-250 Installation and Operation Manual QUICK TEST If the control panel has remote connections to the Fire Department or other monitor, be sure to disable the remote signals and notify the remote monitoring station before performing test operations, since an off-normal condition will be indicated. Quick test is possible in one of two modes, (silent or audible) and is selectable on a perzone basis.
FS-250 Installation and Operation Manual APPENDIX-A: REFERENCE DATA This appendix provides reference for the following topics: • • • Wire selection guides Battery size calculations WIRE SELECTION GUIDES Resistance of Solid Copper Wire AWG Ohms per Thousand Feet* 18 8.08 16 5.08 14 3.19 12 2.01 *NEC Chapter 9, Table 8. Notification Appliance Circuit Wire Selection Guide Each Notification Appliance Circuit must not have a voltage drop greater than 1 volt.
FS-250 Installation and Operation Manual Addressable Device Circuit Wire Selection Guide Each addressable device circuit must meet the following requirements: • • Total loop resistance - 50 ohm maximum with 252 devices.(refer to following graph) Total loop capacitance - 0.5uF max line to line and 1.
FS-250 Installation and Operation Manual BATTERY SIZE CALCULATONS FS-250 Current Calculations Panel and Module Current FS-250 Control Panel (includes one loop driver board)* FS-MT Municipal Tie Standby 0.005 Alarm 0.028 Standby (note 5) Alarm (note 5) FS-DACT DACT Standby 0.038 Board Alarm 0.054 Total Panel currents 0.038 Standby Current (A.) 0.190 + NA + NA + Alarm Current (A.) 0.190 NA + NA + NA 0.054 NA + 0.005 0.
FS-250 Installation and Operation Manual Device Current Calculations Device Current Catalog # Quantity Standby Alarm Standby Alarm Standby Alarm Standby Alarm 4-wire Smoke Detectors Catalog # Quantity Standby Alarm Standby Alarm End of Line Relay Catalog # Quantity Notification Appliances Catalog # Quantity X Current (A.) X = X = X = X = X = X = X = X = Standby Current (A.) Alarm Current (A) + NA NA + + NA NA + + NA NA + + NA NA + X Current (A.) X = X = X = X = + NA + NA NA + NA + X Current (A.
FS-250 Installation and Operation Manual Total System Currents Total Panel and Modules current Total Auxiliary current Total Device current TOTAL PANEL+ Modules + DEVICES STANDBY (A) ALARM (A) + + + + Use the Total Panel+ Modules + Devices for the Battery Size Calculations Battery Size Total Standby Current (from above) A. Total Alarm Current (from above) A. A.H. for Standby A.H.
FS-250 Installation and Operation Manual APPENDIX-B: COMPATIBLE DEVICES DEVICES FOR ADDRESSABLE DEVICE CIRCUITS Siemens P2 Manual Pull Stations Siemens Cat. No. HMS-S HMS-D HMS-M Description Manual Station, Single Action Manual Station , Dual Action Metal Manual Station , Single Action Siemens P2 Modules Siemens Cat. No.
FS-250 Installation and Operation Manual DEVICES FOR NOTIFICATION APPLIANCE CIRCUITS Notification Appliances SIEMENS CATALOG # DESCRIPTION AUDIBLE VOLTAGE (VOLTS) AUDIBLE CURRENT (AMPS) STROBE VOLTAGE (VOLTS) STROBE CURRENT (AMPS) BT-F BF-F CH-F BS-F Bell - Vibrating 21-30 DC 0.110 BT-F BF-F CH-F BS-F Bell - Vibrating 21-30 DC 0.070 BT-SS BF-SS CH-SS BS-SS Bell - Single Stroke 21-30 DC 0.360 U-MCS U-MCS-W U-MCS-AR U-MCS-WE Adapter Strobe 16-33 DC 0.112-0.
FS-250 Installation and Operation Manual SIEMENS CATALOG # DESCRIPTION AUDIBLE VOLTAGE (VOLTS) AUDIBLE CURRENT (AMPS) STROBE VOLTAGE (VOLTS) STROBE CURRENT (AMPS) U-S17S U-17S-W U-S17S-C U-S17S-W-C Sync Strobe Light 20-31 DC 0.059 U-S30S U-S30S-W U-S30S-C U-S30S-W-C Sync Strobe Light 20-31 DC 0.088 U-S60S U-S60S-W U-S60S-C U-S60S-W-C Sync Strobe Light 20-31 DC 0.154 U-S75S U-S75S-W U-S75S-C U-S75S-W-C Sync Strobe Light 20-31 DC 0.
FS-250 Installation and Operation Manual SIEMENS CATALOG # DESCRIPTION AUDIBLE VOLTAGE (VOLTS) AUDIBLE CURRENT (AMPS) STROBE VOLTAGE (VOLTS) STROBE CURRENT (AMPS) U-S17-1 U-S17-1-C U-S17-1-W U-S17-1-W-C U-S17-1-AC U-S17-1-AC-W U-S17-1-AC-C U-S17-1-AC-W-C Strobe Light 20-31 DC 0.059 U-S110-1 U-S110-1-C U-S110-1-W U-S110-1-W-C U-S110-1-AC U-S110-1-AC-W U-S110-1-AC-C U-S110-1-AC-W-C Strobe Light 20-31 DC 0.249 U-S17S-1 U-S17S-1-C U-S17S-1-W U-S17S-1-W-C Sync Strobe Light 20-31 DC 0.
FS-250 Installation and Operation Manual DESCRIPTION AUDIBLE VOLTAGE (VOLTS) AUDIBLE CURRENT (AMPS) STROBE VOLTAGE (VOLTS) STROBE CURRENT (AMPS) U-MMT U-MMT-W U-MMT-AR Electronic Signal8T 20-31 DC 0.024-0.050 (*4) U-MMT-MCS U-MMT-MCS-W U-MMT-MCS-AR Electronic Signal8T w/Adapter 20-31 DC 0.024-0.050 (*4) 16-33 DC 0.112-0.323 U-MMT-S17 U-MMT-S17-W U-MMT-S17-C U-MMT-S17-W-C Electronic Signal8T w/Strobe 20-31 DC 0.024-0.050 (*4) 20-31 DC 0.
FS-250 Installation and Operation Manual DESCRIPTION AUDIBLE VOLTAGE (VOLTS) AUDIBLE CURRENT (AMPS) STROBE VOLTAGE (VOLTS) STROBE CURRENT (AMPS) Electronic Signal8T 12-32 DC 0.020-0.050 (*4) U-EC Electronic Chime 21-30 DC 0.020 U-EC-MCS U-EC-MCS-W Electronic Chime w/Adapter 21-30 DC 0.020 16-33 DC 0.112-0.323 U-EC-S17 U-EC-S17-W Electronic Chime w/Strobe 21-30 DC 0.020 20-31 DC 0.059 U-EC-S30 U-EC-S30-W Electronic Chime w/Strobe 21-30 DC 0.020 20-31 DC 0.
FS-250 Installation and Operation Manual STROBE VOLTAGE (VOLTS) STROBE CURRENT (AMPS) 0.038 16-33 DC 0.112-0.323 21-30 DC 0.038 20-31 DC 0.059 Horn w/Strobe 21-30 DC 0.038 20-31 DC 0.089 Horn w/Strobe 21-30 DC 0.038 20-31 DC 0.155 Horn w/Strobe 21-30 DC 0.038 20-31 DC 0.164 Horn w/Strobe 21-30 DC 0.038 20-31 DC 0.249 21-30 DC 0.038 20-31 DC 0.059 21-30 DC 0.038 20-31 DC 0.088 21-30 DC 0.038 20-31 DC 0.155 21-30 DC 0.038 20-31 DC 0.17 21-30 DC 0.
FS-250 Installation and Operation Manual SIEMENS CATALOG # U-HNH U-HNH-W U-HNH-MCS U-HNH-MCS-W U-HNH-S17 U-HNH-S17-W U-HNH-S30 U-HNH-S30-W U-HNH-S60 U-HNH-S60-W U-HNH-S75 U-HNH-S75-W U-HNH-S110 U-HNH-S110-W U-HNH-S17S U-HNH-S17S-W U-HNH-S30S U-HNH-S30S-W U-HNH-S60S U-HNH-S60S-W U-HNH-S75S U-HNH-S75S-W U-HNH-S110S U-HNH-S110S-W AUDIBLE VOLTAGE (VOLTS) AUDIBLE CURRENT (AMPS) STROBE VOLTAGE (VOLTS) STROBE CURRENT (AMPS) Horn 21-30 DC 0.065 Horn 21-30 DC 0.065 Horn w/Adapter 21-30 DC 0.
FS-250 Installation and Operation Manual AUDIBLE VOLTAGE (VOLTS) AUDIBLE CURRENT (AMPS) STROBE VOLTAGE (VOLTS) STROBE CURRENT (AMPS) Mini-Horn 20-31 DC 0.025 Mini-Horn w/Adapter 20-31 DC 0.025 16-33 DC 0.112-0.323 Mini-Horn w/Strobe 20-31 DC 0.025 20-31 DC 0.059 U-MH-S30 U-MH-S30-W U-MH-S30-C U-MH-S30-W-C Mini-Horn w/Strobe 20-31 DC 0.025 20-31 DC 0.089 U-MH-S60 U-MH-S60-W U-MH-S60-C U-MH-S60-W-C Mini-Horn w/Strobe 20-31 DC 0.025 20-31 DC 0.
FS-250 Installation and Operation Manual SIEMENS CATALOG # DESCRIPTION AUDIBLE VOLTAGE (VOLTS) AUDIBLE CURRENT (AMPS) STROBE VOLTAGE (VOLTS) STROBE CURRENT (AMPS) U-MHT-S30 U-MHT-S30-W U-MHT-S30-C U-MHT-S30-W-C Mini-Horn-S/T w/Strobe 20-31 DC 0.025 20-31 DC 0.089 U-MHT-S60 U-MHT-S60-W U-MHT-S60-C U-MHT-S60-W-C Mini-Horn-S/T w/Strobe 20-31 DC 0.025 20-31 DC 0.155 U-MHT-S75 U-MHT-S75-W U-MHT-S75-C U-MHT-S75-W-C Mini-Horn w/Strobe 20-31 DC 0.025 20-31 DC 0.
FS-250 Installation and Operation Manual APPENDIX-C: TROUBLESHOOTING DEFINITIONS FOR EVENT HISTORY ENTRIES A.
FS-250 Installation and Operation Manual B.
FS-250 Installation and Operation Manual C.
FS-250 Installation and Operation Manual APPENDIX-D: MODULE INSTALLATION INSTRUCTIONS LIST This Appendix provides a list of installation instructions for the following optional modules and accessories: • • • • • • • • • • CAB-BATT FS-MT FS-DACT Battery Box Municipal Tie Board Serial Digital Communicator 315-033917 315-699462 315-699464 FS-NPE FS-RD2 FS-RU2 FS-RE8 FS-SAU2 FS-SAE16 FS-CT2 PAD-3 Optional Transformer Assembly Remote LCD Annunciator Serial Relay Unit Serial Relay Extender Serial Annunciato
FS-250 Installation and Operation Manual APPENDIX-E: GLOSSARY Alarm Signal. A signal indicating an emergency requiring immediate action, such as an alarm for fire from a manual station, a waterflow alarm, or an automatic smoke detector. Alarm Silence Inhibit. An option that prevents a human operator from silencing the notification appliances for a preset period of time. Alarm System.
FS-250 Installation and Operation Manual Initiating Device. A manually or automatically operated device such as a manual pull station, smoke detector, heat detector, waterflow switch or tamper switch. Initiating Device Circuit (IDC). A circuit to which initiating devices are connected. Labeled.
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey Technical Manuals Online! - http://www.tech-man.