FT2011 Floor repeater display Operation Manual MP7/IP7 009311_l_en_-2018-08-29 Building Technologies Control Products and Systems
Imprint Imprint Technical specifications and availability subject to change without notice. Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders will be held liable for payment of damages. All rights created by patent grant or registration of a utility model or design patent are reserved. Issued by: Siemens Switzerland Ltd.
Table of contents 1 About this document ................................................................................... 5 1.1 Displays used in document ............................................................................. 7 1.2 Applicable documents ..................................................................................... 7 1.3 Download center ............................................................................................. 8 1.
| 34 Building Technologies Fire Safety 009311_l_en_-2018-08-29
About this document Displays used in document 1 1 About this document Goal and purpose This document describes the operation of the floor repeater display FT2011 in a fire detection system. The reader shall become familiar with the possible indications and operating functions on the floor repeater display, as well as with the functionality of the floor repeater display in the overall system. This understanding makes an adequate behaviour possible in the event of fire or fault.
1 About this document Displays used in document Document identification The document ID is structured as follows: ID code Examples ID_ModificationIndex_Language_COUNTRY -- = multilingual or international A6V10215123_a_de_DE A6V10215123_a_en_-A6V10315123_a_--_-- Date format The date format in the document corresponds to the recommendation of international standard ISO 8601 (format YYYY-MM-DD).
About this document Displays used in document 1 1.1 Displays used in document The form of display in the document sometimes uses tables.
1 About this document Download center 1.3 Download center You can download various types of documents, such as data sheets, installation instructions, and license texts via the following Internet address: https://siemens.com/bt/download κ Enter the document ID in the search field. You will also find information about search variants and links to mobile applications (apps) for various systems on the home page. 1.
Safety Safety instructions 2 2 Safety 2.1 Safety instructions The safety notices must be observed in order to protect people and property. The safety notices in this document contain the following elements: ● Symbol for danger ● Signal word ● Nature and origin of the danger ● Consequences if the danger occurs ● Measures or prohibitions ffor danger avoidance Symbol for danger This is the symbol for danger. It warns of risks of injury.
2 Safety Safety regulations for the method of operation How risk of injury is presented Information about the risk of injury is shown as follows: WARNING Nature and origin of the danger Consequences if the danger occurs ● Measures / prohibitions for danger avoidance How possible damage to property is presented Information about possible damage to property is shown as follows: NOTICE Nature and origin of the danger Consequences if the danger occurs ● Measures / prohibitions for danger avoidance 2.
Safety Safety regulations for the method of operation 2 CAUTION Noncompliance with the following safety regulations Risk of injury to persons and damage to property ● Compliance with the following regulations is required. ● Specialist electrical engineering knowledge is required for installation. ● Only an expert is permitted to carry out installation work. Incorrect installation can take safety devices out of operation unbeknown to a layperson.
2 Safety Standards and directives complied with Modules and spare parts ● ● ● ● Components and spare parts must comply with the technical specifications defined by Siemens. Only use products specified or recommended by Siemens. Only use fuses with the specified fuse characteristics. Wrong battery types and improper battery changing lead to a risk of explosion. Only use the same battery type or an equivalent battery type recommended by Siemens.
Safety Release Notes 2 2.4 Release Notes Limitations to the configuration or use of devices in a fire detection installation with a particular firmware version are possible. WARNING Limited or non non-existent fire detection Personal injury and damage to property in the event of a fire. ● ● Read the 'Release Notes' before you plan and/or configure a fire detection installation. Read the 'Release Notes' before you carry out a firmware update to a fire detection installation.
3 Features Maximum number of events that can be displayed 3 Features The ↑ floor repeater display is an indication and operating unit in a fire detection installation with the following functions: Indication of events ● ● ● ● 'ALARM' – 'Pre-ALARM' 'Fault' 'Isolation' ↑ 'Technical message' Operation ● Scrolling through lists ● 'Silence buzzer' The ↑ floor repeater display is synchronized with 'Stations' of the configured ↑ visibility and shows the same event texts.
PMI Maximum number of events that can be displayed 4 4 PMI The figure below shows the PMI of a ↑ floor repeater display.
4 PMI Buttons on the PMI 4.1 Buttons on the PMI Navigation buttons The navigation buttons work in the same way as the arrow keys on a PC keyboard. With the buttons <▲> and <▼> it is possible to scroll to the next entry in a list. Switches the buzzer off. By pressing the button, the display changes to the next alarm event. In case of alarm, this button has the same function as the navigation button <▼>. 4.
Service menu 5 5 Service menu Various settings can be performed using a service menu. You can open the service menu using a keyboard shortcut (see corresponding chapter). After calling up the menu and entering a password, the following menu items are available: ● 'Device information' – Shows detailed information on the device. ● 'Buzzer on/off' – Settings of the buzzer. ● 'LED test' – Function test of the LED. ● 'Key test' – Function test for the buttons of the PMI.
6 Operation ALARM Procedure 6 Operation 6.1 ALARM Procedure If your fire detection system has no delayed alarm transmission function ('AVC'), the variant –'Fire Brigade in' 'mm:ss' in Step 1 (see Procedure in the event of alarm) does not apply.
Operation ALARM Procedure 6 Procedure in the event of alarm Step 1 Action / Condition Consequence / Status Read top line on display – 'Fire Brigade requested' 'ALARM' is transmitted to the fire brigade – 'Fire Brigade in' 'mm:ss' 'ALARM' is transmitted to fire brigade in 'mm:ss' Remaining time is shown as Countdown – 'Call Fire Brigade !' If: Remote transmission switched off Remote transmission blocked or defective No remote transmission available Fire brigade must be called by phone! No automatic
6 Operation Procedure in case of Fault 6.2 Procedure in case of Fault Step Action 1 Press on the ↑ Person Machine Interface 2 Read off fault location on display 3 Go to the fault location 4 Eliminate the cause of the fault A list of possible 'Faults' and how they are eliminated can be found in the chapter 'Faults / Troubleshooting' If you cannot eliminate a 'Fault', please contact your service provider.
Operation Open service menu / Select menu item 6 6.4 Open service menu / Select menu item To open the service menu a keyboard shortcut as well as a password are required. The service menu can only be opened when no 'Event' is displayed. Opening the service menu ϖ No 'Event' are displayed. 1. Press , with button pressed. The password dialog is shown. 2. Enter the password and confirm. The service menu is open.
7 Alarm verification concept (AVC) Open service menu / Select menu item 7 Alarm verification concept (AVC) The 'Alarm Verification Concept' serves the purpose of delayed alarm transmission and takes into account the interaction of the operating personnel in the alarming sequence. Operating personnel are able to examine the indicated fire location in the event of a fire alarm. In the event of a ↑ false alarm or ↑ minor incident, the intervention of the fire brigade can be avoided.
Alarm verification concept (AVC) Attendance check 7 7.1 Attendance check Should an event ('Pre-ALARM', 'ALARM') arise, the operating personnel may acknowledge presence within the time t1. After acknowledgement, the investigation time t2 starts. If presence is not acknowledged within the given time t1, ↑ global alarming is activated. 7.
7 Alarm verification concept (AVC) Example of a verification process 7.3 Example of a verification process Alarm verification proceeds as follows: ● An alarm event activates ↑ local alarming and starts the time t1 for attendance check. ● Operating personnel acknowledge 'ALARM' on the operating terminal prior to the expiry of t1. Acknowledging normally silences local alarming (configurable feature). If there is no acknowledgment, ↑ global alarming is activated after the expiry of t1.
Alarm verification concept (AVC) Example of a verification process 7 1 mx m 2 t1.. q t2.. ? qx r rx 3 ..t1 X ..t2 X GA Figure 5: Alarm verification 1 Alarm event q Acknowledge at 'Station' 2 Local alarming qx Not acknowledged 3 Manual call point or on 'Station' t2.. Time t2 to investigate the source of alarm / the fire location mx 'Unmanned operation' operation mode ..t2 X Time t2 has expired m 'Manned operation' operation mode r Reset on 'Station' t1..
7 Alarm verification concept (AVC) Fire alarming 7.4 Fire alarming Alarming is controlled at ↑ 'Area' level. During alarming the ↑ alarming equipment is activated, e.g., ↑ alarm devices and remote transmission devices. Alarm devices For ↑ local and ↑ global alarming, acoustic alarm devices, beacons, digital outputs, etc., can be used. The tone of the alarm devices can be configured differently for local and global alarming (the alarm devices must be suitable for this).
Alarm verification concept (AVC) Fire alarming 7 The alarm devices and the remote transmission can be separately configured for: ● Alarm type (only with automatic zones) – 'Pre-ALARM' – 'ALARM' ● Zone type (only with 'ALARMS') – Manual alarm – Automatic alarm – Degraded fire alarm ● Operation mode: – 'Manned operation' – 'Unmanned operation' ● Alarming type: – 'Local alarming only' – 'Delayed alarming' – 'Global alarming only' Building Technologies Fire Safety 27 | 34 009311_l_en_-2018-08-29
8 Faults / Troubleshooting 8 Faults / Troubleshooting If the ↑ 'Site' displays a 'Fault', the table below provides a list of all possible 'Faults', including information on the possible causes. If a 'Fault' cannot be eliminated with the help of these operation instructions, please contact the service engineer. 'Fault' Cause Remedy 'Automatic detector' 'Detector' missing Re-insert 'Detector' 'Detector' defective Replace 'Detector' with replacement detector.
Maintenance 9 9 Maintenance Please adhere to the local provisions. No maintenance work is required. Cleaning the PMI To clean the PMI use a wet cloth without any cleaning agents, abrasives or solvents.
Glossary Glossary Alarm device Element in the fire detection system for acoustic and/or visual alarming, e.g. alarm sounder, beacon. Alarming control Monitoring and controlling the alarming equipment Alarming equipment Alarm devices and remote transmissions Area The top level in the detection tree. Sections and zones are assigned to the area. Control tree Structure tree with control group and control. Danger level A fire detector signal which conveys the possibility of fire.
Glossary Pre-alarm Stage before an alarm for information early on, should an event occur. Remote transmission Remote transmission. Site Depiction of fire detection installation: The top level in the figure showing the installed system. Combines hardware tree, detection tree, and control tree. Technical message Events (e.g., from third-party systems) evaluated via sensors or contacts which are forwarded to the fire control panel.
Index / Index L A Alarm verification concept AVC .................................................................. Example of verification process ........................ AVC Alarm verification concept ................................ Example of verification process ........................ D 22 24 22 24 LEDs Colors ............................................................... 16 O Original language .................................................. 5 S Source language ........................
Index / Building Technologies Fire Safety 33 | 34 009311_l_en_-2018-08-29
Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies Document ID: 009311_l_en_-Edition: 2018-08-29 © Siemens Switzerland Ltd, 2006 Technical specifications and availability subject to change without notice.