FTI2001-A1 Fire terminal board Mounting Installation MP-UL 1.0 A6V10315040_a_en_US 12/15/2011 Siemens Industry, Inc.
Legal notice Legal notice Technical specifications and availability subject to change without notice. © 2011 Copyright by Siemens Industry, Inc. Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders will be held liable for payment of damages. All rights created by patent grant or registration of a utility model or design patent are reserved.
Table of contents 1 Fire terminal board FTI2001 ..............................................................................5 1.1 Description ...........................................................................................................5 1.2 Installation ............................................................................................................6 1.3 Views ...................................................................................................................
Siemens Industry, Inc.
Fire terminal board FTI2001 Description 1 1 Fire terminal board FTI2001 1.1 Description The fire terminal board FTI2001 is used in the network terminal. The fire terminal board is supplied via a UL Fire Protective Signaling Listed, regulated power supply or via the DC 24 V AUX output of the periphery board of a fire control panel. For uninterrupted operation, the external power source requires battery back-up. Remote displays FT2014 or remote terminals FT2015 are supplied via the auxiliary DC output.
1 Fire terminal board FTI2001 Installation The FTI2001 has the following features: 1.2 Two supply inputs for external DC 24 V supply Two peripheral data bus connections to the PMI & mainboard and to the periphery options Two supervised power limited outputs rated at DC 24 V, 1 A each Installation The fire terminal board FTI2001 is for the network terminal. 2 1 X17 X16 X15 X1 X400 X3 3 Installing the fire terminal board FTI2001 (UL version) 6 Siemens Industry, Inc.
Fire terminal board FTI2001 Installation 1 Holes for securing the fire terminal board on the back box 2 Fire terminal board FTI2001 3 4x fixing screw X1 No connect X3 Connector for operating unit via ribbon cable X15 Connector for power supply output Vsys X16 Connector for supply input Vsys 2 X17 Connector for supply input Vsys X400 Connector for the periphery bus (for options) 1 1. Install the fire terminal board (2) on the back box using the four fixing screws (3). 2.
1 Fire terminal board FTI2001 Views 1.3 Views X17 F203 H204 X16 F204 S1 X15 F202 H203 ON F201 H202 H201 X40 H205 H207 X1 H206 X400 X3 Printed circuit board view of fire terminal board FTI2001 8 Siemens Industry, Inc.
Fire terminal board FTI2001 Views Element Des.
1 Fire terminal board FTI2001 Pin assignments 1.4 1.4.1 Pin assignments Wiring overview The supply must be routed redundantly if the network terminal is supplied in a fail-safe manner via a fire control panel. Two separate supply inputs for redundant supply Two supervised supply outputs for devices on the serial RS485 circuit Power limited acc.
Fire terminal board FTI2001 Indicators 1.4.2 1.4.3 1 X15 Supply output Pin Designation Description 4 GND 2 GND 3 VSYS 2 System supply DC 24 V output (redundant supply) 2 GND 1 GND 1 VSYS 1 System supply output DC 24 V X17/X16 Supply input 1/2 X16, plug-in terminal for supply input 2 (redundant supply input) Pin Designation Description 4 VSYS - 2 GND 3 VSYS - 2 GND 2 VSYS + 2 System supply DC 24 V 1 VSYS + 2 System supply DC 24 V X17, plug-in terminal for supply input 1 1.
1 Fire terminal board FTI2001 Adjustment elements 1.6 Adjustment elements Switch Function Position Meaning S1-1 Supply input 1 'VSYS1' (X17) ON Input 1 is not used (default setting) OFF Input 1 is used (supervised) ON Input 2 is not used (default setting) OFF Input 2 is used (supervised) S1-2 Supply input 2 'VSYS2' (X16) 1.
FCC Statement 2 2 FCC Statement WARNING Installation and usage of equipment is not in accordance with instructions manual Radiation of radio frequency energy Interference to radio communications ● ● Install and use equipment in accordance with instructions manual. Read the following information. This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instructions manual, may cause interference to radio communications.
Issued by Siemens Industry, Inc. Building Technologies Division 8 Fernwood Road Florham Park, NJ 07932 Tel. +1 973-593-2600 www.sbt.siemens.com/FIS Document ID A6V10315040_a_en_US Edition 12/15/2011 © 2011 Siemens Industry, Inc. Technical specifications and availability subject to change without notice. SAP order no.