Specifications
Fire terminal board FTI2001
1
Pin assignments
10
Siemens Industry, Inc. A6V10315040_a_en_US
Building Technologies Division 12/15/2011
1.4 Pin assignments
1.4.1 Wiring overview
The supply must be routed redundantly if the network terminal is supplied in a fail-safe
manner via a fire control panel.
Two separate supply inputs for redundant supply
Two supervised supply outputs for devices on the serial RS485 circuit
Power limited acc. to NFPA 70 / NEC 760
Ground faults detected at <1 kΩ
All wiring in accordance of article 760 of NEC or local building code
-
+
-
+
-
+
-
+
--
++
X400 X3
X17 X16 X15
Input 1 Input 2
To PMI & Mainboard connector on PM
I
To
p
eri
p
heral data bus on PMI
Power sources input 1, 2
FCI2016/17: X1001, AUX 1, 2 (+); 3, 4 (–)
PAD-3
Or UL Fire Protective Signaling Listed,
regulated power supply
AUX +, –
PAD-4 AUX +, –
Output 2
Output 1
S
upervised power limited output
s
Voltage: DC 24 V
Current: 1 A max each
From power supply
Only input 1 is required for power
Input 2 is for redundancy
Supervised for input voltage
Connect only to power limited source
Wiring for fire terminal board FTI2001