Specifications
Fire terminal board FTI2001
1
A
djustment elements
12
Siemens Industry, Inc. A6V10315040_a_en_US
Building Technologies Division 12/15/2011
1.6 Adjustment elements
Switch Function Position Meaning
ON Input 1 is not used (default setting) S1-1 Supply input 1 'VSYS1' (X17)
OFF Input 1 is used (supervised)
ON Input 2 is not used (default setting) S1-2 Supply input 2 'VSYS2' (X16)
OFF Input 2 is used (supervised)
1.7 Technical data
Designation 'VSYS +1', 'VSYS -1'
'VSYS +2', 'VSYS -2'
Voltage DC 24 V
Operating current Max. current 11 mA
Fuse input 1 (F203) 1 Amp Schurter AG, P/N 3404.0116.#
Supply input 1
(Plug X17)
Supply input 2
(Plug X16)
Fuse input 2 (F204) 1 Amp Schurter AG, P/N 3404.0116.#
Designation 'VSYS 1', 'VSYS 2'; 'GND 1', 'GND 2'
Voltage DC 24 V
Current Max. 1 A per output
Supply output
(Plug X15)
Fuses output 1 and 2 (F201, F202) 1 Amp Schurter AG, P/N 3404.0114.#
Supervisory Power limited, supervised for input 1 and 2 voltage
Connection terminals Inputs and outputs
Design Spring clips
Admissible cable cross-section 12…22 AWG