Specifications

Fire terminal board FTI2001
Installation
1
7
Siemens Industry, Inc.
A6V10315040_a_en_US
Building Technologies Division 12/15/2011
1 Holes for securing the fire terminal board on the back box
2 Fire terminal board FTI2001
3 4x fixing screw
X1 No connect
X3 Connector for operating unit via ribbon cable
X15 Connector for power supply output Vsys
X16 Connector for supply input Vsys 2
X17 Connector for supply input Vsys
X400 Connector for the periphery bus (for options)
1. Install the fire terminal board (2) on the back box using the four fixing screws (3).
2. Use the ribbon cable supplied with the operating unit to connect operating unit to
X3.
3. When connecting supplies, make sure no AC is applied. Connect power supply to
X5 Vsys input. If redundancy is needed, also connect power supply to X6 Vsys2
input.
4. Only apply AC after wiring is complete.