FT2080 Fire terminal (Touch) Mounting Installation A6V10462660_en--_b 2016-04-08 Building Technologies Control Products and Systems
Legal notice Legal notice Technical specifications and availability subject to change without notice. Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders will be held liable for payment of damages. All rights created by patent grant or registration of a utility model or design patent are reserved. Issued by: Siemens Switzerland Ltd.
Table of contents Building Technologies Fire Safety 1 Setup of fire terminal (Touch) FT2080 ..................................................... 5 2 Installation in 19" pedestal housing of the FC2080 .................................... 7 3 Installation in housing (standard) .......................................................... 10 4 Installation in rear panel (FT2080) FHA2039 .......................................... 11 5 Installation in desktop housing (FT2080) FHA2040 ...................
| 24 Building Technologies Fire Safety A6V10462660_en--_b 2016-04-08
Setup of fire terminal (Touch) FT2080 1 1 Setup of fire terminal (Touch) FT2080 1 2 3 6 4 4 4 4 6 5 Figure 1: Rear panel fire terminal (Touch) FT2080 Building Technologies Fire Safety 1 Support plate 2 Front indicator (Touch) FTO2010 3 PMI & mainboard FCM2027 4 4x mounting holes in the operating unit 5 Shield plate above carrier (CPU) 6 Hinges for wall housing 5 | 24 A6V10462660_en--_b 2016-04-08
1 Setup of fire terminal (Touch) FT2080 Arrangement of components Figure 2: Components on the fire terminal (Touch) FT2080, without cover cap 1 Front indicator (Touch) FTO2010 2 Main network module (SAFEDLINK) on X13, optional 3 License key, optional 4 Slot 1 [SER_OPT1] for the first serial module at X14, optional 5 Slot 2 [SER_OPT2] for the second serial module at X19, optional 6 Degraded mode network module (SAFEDLINK) on X12, optional 7 CPU module (CORVUS) FCC2009 8 Carrier for CPU mod
Installation in 19" pedestal housing of the FC2080 2 2 Installation in 19" pedestal housing of the FC2080 The installation instructions described below apply to all operating units. Before an operating terminal is installed, the following components must first be mounted on the operating unit.
2 Installation in 19" pedestal housing of the FC2080 5 2x fixing screw 6 PMI & mainboard FCM2027 7 Adapter for power supply (including ribbon cable) 8 Connector strip X3 peripheral data bus connection 1. Plug the network module (SAFEDLINK) (4) into connector X13 (3) of the operating unit (1). 2. Secure the module to mounting flange (2) with both screws (5). Ensure that it is secured correctly to avoid interrupts. 3.
Installation in 19" pedestal housing of the FC2080 2 Wiring the fire terminal (Touch) 3 4 5 2 1 6 Figure 5: Wiring the fire terminal (Touch) with FC2080 1 Ribbon cable for FC2080 system supply to card cage (CPU) X30 2 FCnet connection to card cage (CPU) X11/X12 3 X3 connection to network module (SAFEDLINK) to PMI & mainboard FCM2027 4 Inside of door (section view) 5 Fire terminal (Touch) FT2080 6 Adapter for flat cable of the supply FCnet FCnet Door FC2080 FCC2003 * FCM20xx A1 B1 A2
3 Installation in housing (standard) 3 Installation in housing (standard) Figure 7: Installation of fire terminal in the housing (standard) FH2002 1 Mains connection terminals 2 Power supply unit (70 W) FP2015 3 Rear panel (standard) 4 Fire terminal board FTI2001 5 Wiring FCnet/SAFEDLINK 6 Network module (SAFEDLINK) FN2001 7 Fire terminal (Touch) FT2080 X3 Ribbon cable connection from the fire terminal (Touch) to the fire terminal board X1 Supply input for fire terminal board You will find
Installation in rear panel (FT2080) FHA2039 4 4 Installation in rear panel (FT2080) FHA2039 The rear panel (FT2080) can be used for installation in a desk or installation in a third-party housing. Installing the rear panel (FT2080) in a third-party housing guarantees the required EMC protection.
4 Installation in rear panel (FT2080) FHA2039 Installing fire terminal board FTI2001 2 3 4 1 5 Figure 9: Installing the fire terminal board in the rear cover (FT2080) 1 Rear panel (FT2080) FHA2039 2 Fire terminal board FTI2001 3 4x fixing screws 4 4x mounting holes 5 Threaded press-in sleeves in rear cover (FT2080) 1. Position the fire terminal board (2) in the rear panel (1) as shown. 2.
Installation in rear panel (FT2080) FHA2039 4 Wiring the fire terminal (Touch) When installing in a desktop that is thicker than 33 mm, the cables must be routed through the rectangular openings of the rear panel (FT2080), and not through the round cable breakthroughs.
4 Installation in rear panel (FT2080) FHA2039 Installing the fire terminal (Touch) 2 1 3 4 5 6 7 8 9 Figure 11: Installing the fire terminal (Touch) in the rear panel (Touch) 1 Fire terminal (Touch) FT2080 2 4x fixing screws 3 4x mounting holes in the fire terminal (Touch) 4 Cable lead-through in the rear panel 5 4x threaded holes in the rear cover (FT2080) 6 Lateral cable lead-throughs 7 Rear panel (FT2080) FHA2039 8 Cut-out in the desktop 9 Desktop 1.
Installation in rear panel (FT2080) FHA2039 4 Installing the rear cover (FT2080) in a desktop 3 1 2 4 5 7 6 Figure 12: Installing the rear cover (FT2080) in a desktop 1 Rear panel (FT2080) FHA2039 2 Mounted fire terminal (Touch) FT2080 3 4x fixing screws 4 Mounting holes in the flanges of the rear panel (FT2080) 5 Bores in the desktop 6 Desktop 7 Cutout for rear panel (FT2080) min. 430 x 268 mm 1. Place the rear panel (1) in the cut-out of the desktop (6) as shown.
5 Installation in desktop housing (FT2080) FHA2040 5 Installation in desktop housing (FT2080) FHA2040 1 2 3 5 4 11 6 7 10 9 8 Figure 13: View of desktop housing (FT2080) 1 Top of desktop housing 2 Tilting bracket for top of housing 3 Base of desktop housing 4 M4x10 pan head screw (scope of delivery) 5 Clamping bracket for ground cable (scope of delivery) 6 250 V EMC filter, 3 A with plug-in contacts (mounted) 7 Fixing screw by customer 8 Washer 5/15 mm (scope of delivery) 9 4x ru
Installation in desktop housing (FT2080) FHA2040 5 1. Remove the top of housing (1) by pushing the two tilting brackets (2) on the left and right inwards until you can lift off the top of housing. 2. Connect the ground connection as shown with clamping bracket (5) and M4 pan head screw (4). 3. Place the spacer sleeves (10) from below over the rubber feet (9). 4. Position the housing (3). 5. Place the washers (8) onto the rubber feet (9) inside the housing. 6.
5 Installation in desktop housing (FT2080) FHA2040 Installing fire terminal (Touch) FT2080 2 1 2 1 3 4 3 5 Figure 15: Mounting in top of housing 1 Tilting brackets on left and right for fixing the top of the housing 2 2x fixing screws for tilting brackets and fire terminal 3 2x fixing screws for fire terminal 4 Fire terminal (Touch) FT2080 5 Top of desktop housing (FT2080) FHA2040 1. Place the fire terminal (4) in the top (5) of the desktop housing as shown. 2.
Installation in desktop housing (FT2080) FHA2040 5 Assembly of desktop housing (FT2080) 1 2 3 4 5 6 5 Figure 16: Assembly of desktop housing 1 Fire terminal (Touch) FT2080 2 Top of desktop housing (FT2080) FHA2040 3 Tilting brackets on left and right for fixing the top of the housing 4 Guide cams on left and right for tilting brackets 5 2x threaded holes for fixing the top of the housing 6 Base of desktop housing 7 Fire terminal board FTI2001 1.
5 Installation in desktop housing (FT2080) FHA2040 1 2 3 1 4 Figure 17: Securing the top of the desktop housing 1 Securing cap (scope of delivery) 2 Opening for fixing screw 3 Top of the desktop housing (Touch) 4 Fixing screw with securing device 1. To close the housing, tilt the top of the housing (3) onto the housing and secure the top to the housing using both screws (4). 2.
Installation in desktop housing (FT2080) FHA2040 5 Fire terminal wiring Figure 18: Wiring view of the fire terminal in the desktop housing Building Technologies Fire Safety 1 Fire terminal (Touch) FT2080 2 Network module (FCnet/SAFEDLINK) FN2001 3 Fire terminal board FTI2001 4 Prefabricated cable for supply connection to X7 fire terminal board 5 FCnet connection cable 6 EMC filter 7 Input for DC 24 V system supply to EMC filter 8 Internal cable RJ45 for Ethernet connection, L=420 mm 21
6 Technical data 6 Technical data Supply input Display Interfaces Voltage DC 20…30 V Quiescent current (display illumination dimmed 15%) 390 mA Maximum current (display illumination 100% and lamp test active) 700 mA Screen size 12" Resolution 1280 x 800 pixels 2x slots for serial modules ● ● RS232 module for event printer RS485 module for ESPA-4.4.4 interface, FAT, FBF, UGA or remote EVAC-NL operation 2x slots for network modules (SAFEDLINK) ● Full functionality incl.
Technical data Building Technologies Fire Safety 6 23 | 24 A6V10462660_en--_b 2016-04-08
Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug +41 41-724 24 24 www.siemens.com/buildingtechnologies Document ID: A6V10462660_en--_b Edition: 2016-04-08 © Siemens Switzerland Ltd, 2015 Technical specifications and availability subject to change without notice.