4.4.8 Connecting the inverter with the PM250 Power Module
/LQHILOWHUV 6LQXVILOWHURURXWSXW
UHDFWRU
,QYHUWHU
8
9
:
3( 3(
:
9
8
/
/
/
3( 3(
/
/
/
/
/
/
3(
:
9
8
3(
/
/
/
Figure 4-25 Connecting the PM250 Power Module
Table 4-30 Connection, cross-section and tightening torque for PM250 Power Modules
Inverter Line supply and motor connection Cross-section and tightening torque Stripped
insulation
length
Metric Imperial
FSC Screw-type terminal 4 …10 mm
2
, 2.3 Nm 12 … 8 AWG, 20 lbf in 10 mm
FSD
Cable lug
10 … 35 mm
2
, 6 Nm 7 … 2 AWG, 53 lbf in --
FSE 25 … 50 mm
2
, 6 Nm 3 … 1 AWG, 53 lbf in --
FSF 35 … 120 mm
2
, 13 Nm 2 … 4/0 AWG, 115 lbf in --
Connections for frame size FSC
/LQHVXSSO\ 0RWRU
/ / /
89:
3(
Installing
4.4 Connecting the line supply and motor
Converter with the CU230P-2 Control Units
108 Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF