Operating Instructions

Setting the bus address
Procedure
1. Set the address using one of the subsequently listed options:
Via the address switch
On an operator panel via p0918
With Startdrive
Confirm the prompt for saving your settings (copy RAM to ROM).
2. Switch off the inverter power supply.
3. Wait until all LEDs on the inverter are dark.
4. Switch on the inverter power supply again.
Your settings become effective after switching on.
The PROFIBUS address is set.