When selecting an application class, the inverter assigns the motor control with the appropriate
default settings:
Standard Drive Control (Page 168)
Dynamic Drive Control (Page 170)
Start quick commissioning and select the application class (Page 160)
Depending on the particular Power Module, the inverter skips selecting the application
class. If the BOP-2 does not display step DRV APPL, then continue commissioning as
described under "Expert".
Application class Standard Drive Control Dynamic Drive Control
Properties
Typical settling time after a speed change:
100 ms … 200 ms
Typical settling time after a load surge: 500 ms
6SHHG
/RDG
0RWRU
WRUTXH
W
W
W
PV
"Standard Drive Control" is suitable to
address the following requirements:
Motor power ratings < 45 kW
Ramp-up time 0 → rated speed
(depending on the motor power rating):
1 s (0.1 kW) … 10 s (45 kW)
Applications with increasing load torque
without load surges
"Standard Drive Control" is insensitive with
respect to imprecise setting of the motor data
Typical settling time after a speed change:
< 100 ms
Typical settling time after a load surge: 200 ms
6SHHG
/RDG
0RWRU
WRUTXH
W
W
PV
"Dynamic Drive Control" controls and limits the
motor torque
Torque accuracy that can be achieved: ± 5% for
15 % … 100 % of the rated speed
We recommend "Dynamic Drive Control" for the
following applications:
Motor power ratings > 11 kW
For load surges 10 % >100 % of the rated
motor torque
"Dynamic Drive Control" is necessary for a ramp-
up time 0 rated speed (dependent on the rated
motor power): < 1 s (0.1 kW) … < 10 s (132 kW).
Application exam‐
ples
Pumps, fans, and compressors with flow
characteristic
Pumps and compressors with displacement
machines
Power Modules
that can be operat‐
ed
PM240‑2, PM240P-2 PM240‑2, PM240P-2 PM330
Max. output fre‐
quency
550 Hz 240 Hz 150 Hz