Operating Instructions

6.8 Drive control via Ethernet/IP
EtherNet/IP is an Ethernet-based fieldbus. EtherNet/IP is used to transfer cyclic process data
as well as acyclic parameter data.
Settings for Ethernet/IP
Parameter Explanation
p2030 = 10 Fieldbus interface protocol selection: Ethernet/IP
p8920 PN Name of Station
p8921 PN IP address (Factory setting: 0)
p8922 PN default gateway (factory setting: 0)
p8923 PN Subnet Mask (Factory setting: 0)
p8924 PN DHCP mode (Factory set‐
ting: 0)
0: DHCP off
2: DHCP on, identification based on MAC address
3: DHCP on, identification based on Name of Station
p8925 PN interface configuration
(Factory setting: 0)
0: No function
1: Reserved
2: Save the configuration and activate
3: Delete configuration
p8980 Ethernet/IP profile (Factory setting: 0)
A change only becomes effective after the inverter power
supply has been switched off and switched on again.
0: SINAMICS
1: ODVA AC/DC
p8982 Ethernet/IP ODVA speed scaling (Factory setting: 128)
A change only becomes effective after the inverter power supply has been switched off
and switched on again.
123: 32
124: 16
125: 8
126: 4
127: 2
128: 1
129: 0.5
130: 0.25
131: 0.125
132: 0.0625
133: 0.03125
Further information
Further information about USS is provided in the "Fieldbus" function manual.
Overview of the manuals (Page 538)
Advanced commissioning
6.8 Drive control via Ethernet/IP
Converter with the CU230P-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF 245