Operating Instructions

Article No. 6SL3310- 1PE38-4AA0 1PE38-8AA0 1PE41-0AA0
Required cooling air flow 450 l/s 450 l/s 450 l/s
Maximum connectable cross-section of the power
cable
6 x 240 mm
2
6 x 500 kcmil
6 x 240 mm
2
6 x 500 kcmil
6 x 240 mm
2
6 x 500 kcmil
Maximum connectable cross-section of the motor
cable
4 x 240 mm
2
4 x 500 kcmil
8 x 240 mm
2
8 x 500 kcmil
8 x 240 mm
2
8 x 500 kcmil
Maximum connectable cross-section of the DC link
cable
4 x 240 mm
2
4 x 500 kcmil
4 x 240 mm
2
4 x 500 kcmil
4 x 240 mm
2
4 x 500 kcmil
Recommended cable cross-section for 380 V/400 V
- line cable
- motor cable
3)
4 x 185 mm
2
4 x 150 mm²
4 x 185 mm
2
4 x 185 mm²
4 x 240 mm
2
4 x 240 mm²
Recommended cable cross-section for 480 V
- line cable
- motor cable
3)
4 x 120 mm
2
4 x 120 mm²
4 x 150 mm
2
4 x 150 mm²
4 x 185 mm
2
4 x 150 mm²
Recommended cable cross-section for 380 V/400 V
- DC link infeed (2/3 inverter power)
- Braking Module
4)
4 x 120 mm
2
35 mm²
4 x 150 mm
2
35 mm²
4 x 185 mm
2
35 mm²
Recommended cable cross-section for 480 V
- DC link infeed (2/3 inverter power)
- Braking Module
4)
3 x 120 mm
2
35 mm²
3 x 150 mm
2
35 mm²
3 x 185 mm
2
35 mm²
Tightening torque for line, motor, DC link, and
ground cable
50 Nm / 443 lbf in 50 Nm / 443 lbf in 50 Nm / 443 lbf in
Dimensions: Width x height x depth [mm] 801 x 1621 x 393 801 x 1621 x 393 801 x 1621 x 393
Weight 235 kg 250 kg 250 kg
1)
The line supply must be capable of supplying the minimum short-circuit current so that the fuses trigger and consequential
damage is avoided.
Note: If the minimum short-circuit current is not reached, then the tripping time for the fuses increases, and this may result
in consequential damage.
2)
When semiconductor fuses are used, they must be mounted in the same higher construction as the inverter.
3)
The motor cables must be evenly distributed at both connection chambers.
4)
For connection of the Braking Module with rated power of 50 kW, P
20
power of 200 kW.
Technical data
10.5 Technical data, PM330 Power Module
Converter with the CU230P-2 Control Units
476 Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF