Operating Instructions

Table 10-52 PM240-2, PT, frame size A, 380 V … 480 V 3 AC
Article No. without filter
Article No. with filter
6SL3211-1PE18-0UL1
6SL3211-1PE18-0AL1
LO base load power 3.0 kW
LO base load input current 10.1 A
LO base load output current 7.7 A
HO base load power 2.2 kW
HO base load input current 8.8 A
HO base load output current 5.9 A
Fuse according to IEC
Fuse according to UL, class J
3NA3805 (16 A)
30 A
Power loss without filter 0.12 kW
1)
Required cooling air flow 7 l/s
Weight without filter 1.8 kg
Weight with filter 2.0 kg
1) approx. 0.1 kW through the heatsink
Table 10-53 PM240-2, IP20, frame size B, 380 V … 480 V 3 AC
Article No. without filter
Article No. with filter
6SL3210-1PE21-1UL0
6SL3210-1PE21-1AL0
6SL3210-1PE21-4UL0
6SL3210-1PE21-4AL0
6SL3210-1PE21-8UL0
6SL3210-1PE21-8AL0
LO base load power 4.0 kW 5.5 kW 7.5 kW
LO base load input current 13.3 A 17.2 A 22.2 A
LO base load output current 10.2 A 13.2 A 18.0 A
HO base load power 3.0 kW 4.0 kW 5.5 kW
HO base load input current 11.6 A 15.3 A 19.8 A
HO base load output current 7.7 A 10.2 A 13.2 A
Fuse according to IEC
Fuse according to UL, class J
3NA3812 (32 A)
35 A
3NA3812 (32 A)
35 A
3NA3812 (32 A)
35 A
Power loss 0.11 kW 0.15 kW 0.2 kW
Required cooling air flow 9.2 l/s 9.2 l/s 9.2 l/s
Weight without filter 2.9 kg 2.9 kg 3.0 kg
Weight with filter 3.1 kg 3.1 kg 3.2 kg
Technical data
10.6 Technical data, PM240-2 Power Module
Converter with the CU230P-2 Control Units
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257946B AF 495