Operating Instructions

Parameter Description
p20158 = 722.0 Connect the status of DI 0 to the input of the time block
r0722.0 = Parameter that displays the status of digital input 0.
p20030[0] = 20160 Interconnecting the time block to the 1st AND input
p20030[1] = 722.1 Interconnecting the status of DI 1 to the 2nd AND input
r0722.1 = Parameter that displays the status of digital input 1.
p0840 = 20031 Interconnect the AND output to ON/OFF1
Explanation of the application example using the ON/OFF1 command
Parameter p0840[0] is the input of the "ON/OFF1" block of the inverter. Parameter r20031 is
the output of the AND block. To interconnect ON/OFF1 with the output of the AND block, set
p0840 = 20031.
212))
S>@
S>@ 
S>@

U
$1'
Figure A-7 Interconnecting blocks by setting p0840[0] = 20031
Appendix
A.3 Interconnecting signals in the converter
Converter with the CU230P-2 Control Units