G120P Variable Speed Drive Technical Manual A5E36496664A_f 2021-10-11 Smart Infrastructure
Imprint Imprint Technical specifications and availability subject to change without notice. Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders will be held liable for payment of damages. All rights created by patent grant or registration of a utility model or design patent are reserved.
Table of contents 1 History of changes ................................................................................... 5 2 2.1 2.2 2.3 About this documentation........................................................................ 6 Purpose of this documentation ........................................................................... 6 Reference sources for documents ..................................................................... 8 Product documentation .....................................
6.4 6.5 6.6 6.7 Carrying out basic commissioning ................................................................... 55 Configuring communication ............................................................................. 70 Additional settings............................................................................................. 74 6.6.1 Restoring parameters to factory settings ........................................ 74 6.6.2 Setting the PID controller ...........................................
History of changes 1 1 History of changes The table below shows this document's history of changes: Version Edition date Brief description f 2021-10-11 Complete revision and introduction IOP-2-BT e 2017-01-24 Neutral concerning FW and version of related documentation d 2016-03-18 FW4.7 SP6 HF1 c 2015-01-06 FW4.7 SP3 b 2014-05-16 FW4.7 a 2013-03-19 First edition, FW4.
2 About this documentation Purpose of this documentation 2 About this documentation 2.1 Purpose of this documentation This Operating Manual provides a summary of all of the information required to operate the SINAMICS G120P variable speed drive (referred to below as "variable speed drive" or "device") under regular, safe conditions. For further information, that is, all other relevant documentation, please refer to Chapter Product documentation [➙ 8].
About this documentation Purpose of this documentation Examples of how safety instructions are displayed in this document 2 Example of a danger notice for hazardous voltages, which, if ignored, will result in death or serious injuries. DANGER Type and source of the danger Consequences of failing to heed the danger ● Measures to avoid the danger Example of a danger notice for moving parts, which, if ignored, may result in death or serious injuries.
2 About this documentation Reference sources for documents 2.2 Reference sources for documents Siemens Industry Online Support (SIOS) Various document types, such as data sheets, operating instructions, assembly instructions and license texts can be found in the SIOS portal (Siemens Industry Online Support) at https://support.industry.siemens.com. If required, a user account can be created here first. The individual entries for documents, announcements, technical articles, etc.
About this documentation Product documentation 2 2.3 Product documentation Title Description Source/Document ID Operating Manual Design, installation, commissioning and troubleshooting the SINAMICS G120P. A5E36496664A Hardware Installation Guide with all the information needed to install, Manual mount, connect, and service SINAMICS G120P Power Module PM230 systems.
3 Safety Intended use 3 Safety General warnings, precautionary measures and hazard instructions which apply when working with the device are summarized below. Safety information which only applies to certain tasks is listed at the start of every section or is repeated or added at critical points within these sections. 3.1 Intended use The SINAMICS G120P variable speed drive described in these Operating Instructions is a device for controlling an induction motor.
Safety Safety equipment 3 3.2 Safety equipment WARNING Danger to life due to safety equipment malfunctions! If safety equipment fails to function properly or is deactivated or disabled, the device can pose a risk of extremely serious injury or death. Failure to provide a proper protective conductor connection can affect the ability of protective equipment to function correctly. ● Ground the device in compliance with the applicable regulations.
3 Safety Personnel requirements 3.3 Personnel requirements All personnel must be persons who can reasonably be expected to work reliably and conscientiously. Persons whose ability to react is impaired, for example, by drugs, alcohol or medication, are prohibited from working with the device. The regulations pertaining to age and occupation applicable at the site of installation must be observed in the selection of personnel.
Safety Residual risks 3 3.5 Residual risks A description is given below of the residual risks potentially posed by variable speed drives even when they are used for their intended purpose. Please observe the safety information provided below and safety guidance contained in other sections of these Operating Instructions in order to reduce the risk to personnel and property and prevent potentially hazardous situations. 3.5.
3 Safety Residual risks DANGER Danger to life when live parts on damaged devices are touched! Improper handling of devices can cause damage. ● Ensure compliance with the limit values specified in the technical data during transport, storage and operation. ● Do not use any damaged devices.
Safety Residual risks 3 WARNING Danger to life due to moving (rotating) mechanical parts! When the variable speed drive is switched on, the motor may start up unexpectedly. Contact with moving parts can cause severe physical injuries and serious property damage. ● Only touch these parts when the machine is at a standstill.
3 Safety Residual risks WARNING Danger to life due to fire if overheating occurs because of insufficient ventilation clearances! Insufficient ventilation clearances can result in overheating with danger to persons as a result of smoke and fire. This can also result in increased downtime and reduced service lives for devices and systems. ● Ensure compliance with the specified minimum clearances as ventilation clearances for the relevant components.
Safety Residual risks 3.5.6 3 Dangers due to inactive safety functions DANGER Danger to life due to inactive safety functions! Inactive or non-adapted safety functions can trigger machine malfunctions that cause serious injury or death. ● Install the device as instructed in this document. ● Carry out a safety assessment of all safety-relevant functions of the entire system, including all safety-related components.
3 Safety Handling electrostatic discharge sensitive devices 3.6 Handling electrostatic discharge sensitive devices Electrostatic sensitive devices (ESD) are individual components, integrated circuits, modules, or devices that may be damaged by either electrostatic fields or electrostatic discharges.
Product information Product description 4 4 Product information 4.1 Product description SINAMICS G120P variable speed drives provide open-loop and closed-loop speed control functions for pump and fan motors in building management applications. The variable speed drive is modular in design. The following components are combined to create the SINAMICS G120P variable speed drive: ● CU230P-2-BT Control Unit: Controls and monitors the Power Module and the connected motor.
4 Product information Product description NOTICE The operator panel or blanking cover is not included in the standard scope of supply and must be ordered separately.
Product information Components 4 4.2 Components Below you will find all the information you need to know about the SINAMICS G120P variable speed drive and its components, together with a description of potential applications.
4 Product information Components 4.2.1 CU230P-2-BT Control Unit Figure 5: CU230P-2-BT Control Unit Item Designation 1 Slot for memory card (MMC or SD card) 2 Operator panel interface (IOP-2-BT, BOP-2 or SAM) 3 DIP switches for fieldbus address, incl.
Product information Components Item Designation 8 Digital outputs 9 Terminal strip 10 Terminal designation 4 Details Chapter Wiring terminal strips [➙ 44] The fieldbus interfaces are located on the bottom of the Control Unit.
4 Product information Components 4.2.2 PM230 Power Module The PM230 Power Module is designed for applications involving pumps, fans and compressors with a square characteristic. The PM230 Power Module is available in the following versions: Criterion Version Frame size FSA-FSF (Framesize A – Framesize F) Filter A: Power Modules with integrated filter Class A can be deployed in installations according to EN 61800-3 categories C3 and C2.
Product information 4 Components 4.2.3 Operator panels Operator panels are used to commission, diagnose and control the variable speed drive. Use of an operator panel is optional. If an operator panel is not required, it can be replaced by a blanking cover. A variable speed drive without an operator panel is commissioned via an external computer on which the "STARTER" software is installed.
4 Product information Components Operator controls and screen symbols IOP-2-BT - operator controls Button Description Navigation-sensor field: ● ● Change selection Change parameters – Clockwise rotation increases the value – Counter-clockwise rotation reduces the value Pressing the button: ● Confirm selection Pressing and holding down the button (> 3 s) ● Toggle between changing individual digits and changing the whole value ● In AUTO mode: no function ● In MANUAL mode: pressing starts the v
Product information Components IOP-2-BT - screen symbols Function Status Command source Auto Auto - the converter receives the command signals from the network controller JOG Is displayed if the JOG function is activated Manual Hand - the converter is under control of the IOP-2-BT Variable speed drive state Symbol 4 Comments Ready In operation Symbol rotates when the motor is running.
4 Product information Components BOP-2 - operator controls Button Function ● Pressing the button: Confirm selection ● Pressing and holding down the button (> 3 s): Toggle between changing individual digits and changing the whole value ● ● ● Pressing the button: – Scroll up through the menu – Increase a parameter value Pressing the UP and DOWN buttons simultaneously when MANUAL and JOG mode are activated: Switch the reverse function on and off Pressing the button: – Scroll down through the men
Product information Components SAM - operator controls Button Reset WLAN 4 Function ● Holding down the button for more than three seconds when the SINAMICS G120 Smart Access is in power-on state resets the Wi-Fi configuration of the SINAMICS G120 Smart Access to factory defaults.
4 Product information License terms 4.3 License terms The variable speed drive contains open source software (OSS). The license terms for the open source code are stored in the variable speed drive. Transferring the license terms To transfer the OSS license terms from the variable speed drive to a PC, proceed as follows: 1. Switch off the variable speed drive power supply. 2. Insert an empty memory card into the card slot of the variable speed drive. 3. Switch on the variable speed drive power supply. 4.
Installing Safety instructions for installation 5 5 Installing 5.1 Safety instructions for installation DANGER Risk of injury due to hazardous voltages! Variable speed drives are at hazardous voltage levels and control the speed and direction of rotation of motors. Touching live parts can result in serious physical injury or death. ● Make sure that the variable speed drive is installed and commissioned by qualified personnel.
5 Installing Overview of installation NOTICE Danger of property damage due to unsuitable site of installation! Unsuitable ambient conditions can damage the device by impairing its ability to function properly. ● Only install the variable speed drive in areas which are free from jolts, vibrations, electromagnetic fields, and corrosive gases. ● Maintain the ambient conditions which are specified in the technical data, such as temperature, pressure, humidity, etc. (Chapter Technical data [➙ 111]).
Installing Installing the Power Module 5 5.3 Installing the Power Module 5.3.1 Installing Power Modules For information about dimensions, drilling templates, minimum clearances and tightening torques, please refer to the Operating Instructions for the Control Unit A5E34257946B, SIOS-Entry-ID: 109782866. IP20 devices IP20 devices must be protected against conductive pollution, e.g., by installing them in a control cabinet with IP54 degree of protection according to IEC 60529 or NEMA 12.
5 Installing Installing the Power Module 5.3.2 5.3.2.1 Connecting line and motor terminals Overview of line and motor connections The following diagrams show the arrangements of the line and motor terminals on the relevant Power Module of frame sizes FSA to FSF. The permissible tightening torques for terminals are listed in the table titled "Overview of tightening torques". IP20 FSA...
Installing Installing the Power Module 5 IP20 FSD...FSF 1 2 Figure 9: IP20 FSD-FSF Item Designation 1 Power supply 2 Motor connection IP55 FSA...
5 Installing Installing the Power Module IP55 FSD...FSF Figure 11: IP55 FSD-FSF Item 1 Designation Item 2 Connection of supply voltage Designation Motor connection Overview of tightening torques FSA FSB FSC FSD FSE FSF IP20 0.4 Nm... 0.5 Nm 0.55 Nm... 0.6 Nm 1.2 Nm... 1.5 Nm 6 Nm 6 Nm 13 Nm IP55 0,5 Nm (4,4 lbf.in) 0,6 Nm (5,3 lbf.in) 1,5 Nm (13,3 lbf.in) M6: 6 Nm (53,0 lbf.in) M6: 6 Nm (5,3 lbf.in) M8: 13 Nm (115 lbf.in) Table 9: Overview of tightening torques 5.3.2.
Installing Installing the Power Module Cross sections of power cables Frame size FSA FSB FSC FSD FSE FSF Cable cross-section of the grounding conductors ● ● ● ● Cable types Rating Cable cross-section 2 5 Tightening torques kW mm AWG Nm lbf in 0.37...1.5 1.0 … 2.5 18…14 0.5 4.4 2.2...3 1.5…2.5 16…14 0.5 4.4 4 2.5…6.0 14…10 0.6 5.3 5.5...7.5 4.0…6.0 12…10 0.6 5.3 11 6.0 … 16 10 … 5 1.5 13.3 15...18.5 10 … 16 7…5 1.5 13.3 22.0...30 10...35 5...
5 Installing Installing the Power Module Cable preparation 1. Expose the shield around the length C in order to ensure that devices with an EMC filter of Class B conform to EMC category C1. 2. When the cable is fed through the base plate, also expose the shield around the length D (see sketch above, at the end of "D") and insert the cable through the conductively connected EMC cable gland. 5.3.2.
Installing Installing the Power Module 5 Accessing line and motor terminals If a terminal cover is fitted, please follow the instructions below in order to access the line and motor terminals: 1. Loosen the safety catch on the sides of the terminal cover using a suitable size of flat-head screwdriver. 2. Turn the terminal cover up and allow it to engage. For information about line and motor connections, please refer to Chapter Overview of line and motor connections [➙ 34].
5 Installing Installing the Power Module Connecting the motor cable to the variable speed drive To connect the motor cable to the variable speed drive, proceed as follows: 1. Open the terminal covers (if fitted) of the variable speed drive. 2. Connect the motor at terminals U2, V2 and W2. Follow the instructions pertaining to EMC-compliant wiring (Chapter EMC-compliant installation (examples) [➙ 47]). 3. Connect the protective conductor of the motor to terminal PE of the variable speed drive. 4.
Installing Installing the Power Module 5 Figure 14: Removing the gland plate 3. Fasten the cable glands to the cables. Figure 15: Fastening cable glands 4. Ensure that the screws on the cable glands are loosened so that the cables slide through unhindered. 5. Attach a ferrite core to the motor cable (applies only to Class B filter variants, see "Attaching ferrite rings to motor and line cables"). 6. Attach the power and motor cable to the terminals of the Power Module.
5 Installing Installing the Power Module Attaching ferrite rings to motor and line cables Where ferrite rings are required, they are included in the scope of supply for the product. Motor cable In the case of PM230 Power Modules of frame sizes FSA to FSC (0.75 kW...15 kW) with integrated Class B filters, attach the colored ferrite ring to the motor power cable in order to meet the requirements set out in EMC category C1 for conducted interference emissions.
Installing Installing the Control Unit Item 5 Designation 1 Colored ferrite ring 2 Colored ferrite ring 3 Colored ferrite ring ● 1 x ferrite ring ● 1 x large cable clamp 4 Colored ferrite ring 5 Colored ferrite ring ● 2 x ferrite ring ● 3 x cable ties 5.4 Installing the Control Unit 5.4.
5 Installing Installing the Control Unit Installing the Control Unit on an IP55 Power Module Figure 17: Installing the Control Unit - IP55 The Power Module has been correctly mounted (Chapter Installing the Power Module [➙ 33]). The device is de-energized. 1. Unscrew the cover of the Power Module. 2. Locate the lugs at the rear of the Control Unit in the matching recesses of the Power Module. 3. Mount the Control Unit onto the Power Module so that it audibly snaps into place. 4.
Installing Installing the Control Unit 5.4.2 5 Wiring terminal strips To access the interfaces on the Control Unit, you must remove the operator panel (if one is being used) and open the front doors. The terminal settings depend on the application. For more information, refer to Chapter Application examples [➙ 82]. 5.4.2.1 Overview of terminal strips Figure 18: Terminal strips 1-3 Item Siemens Smart Infrastructure Description 1 The analog input is supplied from an external 10 V voltage.
5 Installing Installing the Control Unit Figure 19: Terminal strips 4-6 Item 4 Description Wiring when using external power supplies. Connecting a contact switching to P. 5 Wiring when using the internal power supplies. Connecting a contact switching to M. 6 Wiring when using external power supplies. Connecting a contact switching to M. 5.4.2.
Installing Installing the operator panel 5 7. Route the signal cables in such a way that you can completely close the front doors after wiring the terminal strip. 8. If you use shielded cables, then you must connect the shield to the mounting plate of the control cabinet or to the shield support of the variable speed drive through a good electrical connection and a large surface area. See also: EMC design guidelines (SIOS Entry-ID: 60612658). 9. Use strain relief. 5.
5 Installing EMC-compliant installation (examples) 5.6 EMC-compliant installation (examples) Variable speed drives are designed for operation in industrial environments where a high level of electromagnetic interference is likely to be present. Safe, reliable and disturbance-free operation is only guaranteed if the variable speed drive is installed professionally and in compliance with EMC regulations, see also EMC design guidelines, SIOS Entry-ID: 60612658.
Installing 5 EMC-compliant installation (examples) EMC-compliant wiring for Power Modules with degree of protection IP20 Install and operate variable speed drives with IP20 degree of protection in a closed control cabinet.
5 Installing EMC-compliant installation (examples) Using two examples, the following diagram shows the EMC-compliant installation of the Power Module with and without shield plate. You must use the shield plate to achieve EMC-compliant installation of devices in frame sizes FSA to FSC. The shield of the control cable must be attached to both the shield plate of the Control Unit and the shield plate of the Power Module.
Installing EMC-compliant installation (examples) 1 2 5 3 4 Item Siemens Smart Infrastructure Designation 1 Expose the cable shield 2 Press cable shield onto the shield/mounting plate 3 Shield plate 4 Mounting plate 51 | 118 A5E36496664A_f 2021-10-11
5 Installing EMC-compliant installation (examples) EMC-compliant wiring for Power Modules with degree of protection IP55 Variable speed drives with degree of protection IP55 are suitable for installation outside a control cabinet.
Installing EMC-compliant installation (examples) 5 Figure 24: EMC-compliant wiring IP55 Item ● ● ● ● Siemens Smart Infrastructure Designation Item Designation 1 Strain relief 7 EMC gland (essential for Class B filters) 2 Line supply cable, unshielded 8 Shielding 3 Good conductive connection for highfrequency EMC interference 9 Motor cable shield 4 Standard cable gland 10 Shield bonded over large area 5 EMC gland 11 Control Unit control cable 6 Shielded motor cable Use a shield
6 Commissioning Safety instructions for commissioning 6 Commissioning 6.1 Safety instructions for commissioning WARNING Risk of injury due to uncontrolled movements! Loads can move uncontrollably when the connected motor is switched on for the purpose of motor data identification. These movements can cause serious injury. ● Before switching on, check that no parts are loose on the machine or can be spun out.
Commissioning Preparing for commissioning 6 6.
6 Commissioning Carrying out basic commissioning Commissioning with BOP-2 For further information on technical data, commissioning and operation of the G120P with BOP-2, see A5E37143404B, SIOS Entry-ID: 109483379. To enter the data for basic commissioning with the BOP-2, proceed as follows: 1. Press the keys ESC, and to navigate to the SETUP menu. 2. To start the basic commissioning process, press . 1.
Commissioning Carrying out basic commissioning 6 The motor data settings for ● rated voltage in volts ● rated current in amperes ● shaft output in KW or hp ● rated frequency in Hz ● rated speed in RPM from the rating plate must match the wiring (star/delta). 1. Press to change the parameter value. 2. Use keys and (or alter individual digits by pressing order to change the displayed value. 3. Press for 3 seconds) in to confirm the setting.
6 Commissioning Carrying out basic commissioning You can specify an alternative ramp-down time if necessary. Activates the motor data identification process. A motor ID process is compulsory if the CTRL MODE (P1300) has been set to 20 (Sensorless Vector Control). Motor data identification is initiated when the drive is first enabled following basic commissioning.
Commissioning Carrying out basic commissioning 6 Commissioning with IOP-2-BT For further information on technical data, commissioning and operation of the G120P with IOP-2-BT, see A5E39549448B, SIOS Entry-ID: 109781592.
6 Commissioning Carrying out basic commissioning 60 | 118 Siemens Smart Infrastructure Factory Reset begins Select Motor Standard Select mains frequency and units Select Motor Type Select Input Mode Enter Motor Data or Motor Code Select Supply Voltage Enter Supply Voltage from rating label Select Motor Current Enter Motor Current from rating label Select Motor Power Enter Motor Power from rating label A5E36496664A_f 2021-10-11
Commissioning Carrying out basic commissioning Select Motor Speed Enter Motor Speed from rating label Select Motor Voltage Enter Motor Voltage from rating label Select Motor Frequency Enter Motor Frequency Select Min. Freq. Enter the required Min. Freq. Select Max. Freq. Enter the required Max. Freq.
6 Commissioning Carrying out basic commissioning 62 | 118 Siemens Smart Infrastructure Select Ramp-down Time Enter required Ramp-down Time Select I/O Setup Select the required Macro Save the Settings Saving Settings in progress Settings have been saved Motor ID ran on next ON command Setup up completed A5E36496664A_f 2021-10-11
Commissioning Carrying out basic commissioning 6 Commissioning with SAM For further information on technical data, commissioning and operation of the G120P with SAM, see SIOS Entry-ID: 109781592. You can open the quick setup Web page by selecting the quick setup icon from either the home page or the navigation sidebar to do the quick commissioning of the converter. The quick setup icon may vary depending on the connected converters.
6 Commissioning Carrying out basic commissioning Expanded page for classic quick setup When you see the Expand sidebar on the far left of the classic quick setup page, click the sidebar and an expanded quick setup page opens. You can do the following on this page: ● View the status of individual quick setup steps based on the symbols given below: Completed step Current step To-be-completed step ● Go back to a completed step.
Commissioning Carrying out basic commissioning 6 3. Select an application class according to the particular converter connected. If required, click relevant application class to expand the detailed description. If "Expert" is selected, you can select your control mode of the converter. 4. Set the required motor data. For Siemens motors, enter only the motor data as shown in ④ and the SINAMICS G120 Smart Access will automatically identify the rest of the motor data.
6 Commissioning Carrying out basic commissioning 5. Select the factory interface settings for the converter based on your particular application. Note that the factory interface settings vary depending on the connected converter.
Commissioning Carrying out basic commissioning 6 6. Set the following parameters based on your particular application. - Minimum speed - factory setting 0 [rpm] The minimum speed is the lowest speed of the motor independent of the speed setpoint. - Maximum speed - factory setting 1500 [rpm] The converter limits the motor speed to the maximum speed. Siemens Smart Infrastructure - The ramp-up and ramp-down times define the maximum motor acceleration when the speed setpoint changes.
6 Commissioning Carrying out basic commissioning 7. Select the desired technological application. Depending on the selected application class, the available technological applications may vary.
Commissioning Carrying out basic commissioning 6 8. Select the method which the converter uses to measure the data of the connected motor.
6 Commissioning Configuring communication 6.5 Configuring communication You are currently performing, or have already completed, basic commissioning. 1. When you reach the appropriate stage of basic commissioning, select the macro (MacPar) 108 (USS fieldbus), 109 (Modbus), 110 (BACnet) or 114 (P1 fieldbus). 2.
Commissioning Configuring communication Setting the address 6 1. Set the variable speed drive's fieldbus address either using the DIP switch on the Control Unit or via parameter p2021. 2. Please refer to Chapter CU230P-2-BT Control Unit [➙ 22] for the position and setting of the DIP switch. If you have set a valid address using the DIP switch, this address always remains valid and p2021 cannot be changed. If you set all DIP switches to "OFF" (0), then p2021 defines the address.
6 Commissioning Configuring communication Modbus RTU protocol Parameter Description p0015 Select value 109 "Modbus RTU" during basic commissioning. p2021 Valid Modbus RTU addresses: 1…247 Invalid Modbus RTU address: 0 p2020 Fieldbus baud rate p2024 p2029 ● Baud rates from 4800 bps to 187500 bps can be set for communication. ● Factory setting: 19200 bps Modbus timing ● Index 0: Maximum slave telegram processing time Maximum response time from the slave to the master.
Commissioning Configuring communication 6 Parameter Description p2025 BACnet communication parameter The device object ID (p2025[0]) must be greater than 1 in the case of firmware < 4.6. ● [0]: 0…4194303, device object instance number Factory setting: 1 ● [1]: 1…10, maximum info frames Factory setting: 1 For optimum performance, this value should be set to 10.
6 Commissioning Additional settings P1 FLN Parameter Value Description p0015 114 Select value 114 "P1 communication" during basic commissioning. p2020 5 Baud rate 4800 bps, alternative setting option for P1: p2020 = 6 (9600 bps) p2021 1 … 99 Slave address (factory setting = 99) The "Point numbers" defined in the device for communication via P1 can be found in the Operating Instructions for the Control Unit (A5E34257946B).
Commissioning Additional settings 6 The communication settings and the settings of the motor standard (IEC/NEMA) are retained after resetting. Proceed as follows to reset the variable speed drive to its factory settings: STARTER software 1. Go online with STARTER. 2. Click the IOP-2-BT button. 1. Select Options > Parameter settings > Reset drive to factory settings. 2. Confirm with OK. BOP-2 1. Select Options > DRVRESET in the menu. 2. Confirm with OK.
6 Commissioning Additional settings 6.6.2 Setting the PID controller Setting the PID controller If the PID controller is activated, the set ramp times are bypassed in p1120 and p1121 (applies only to FW < V4.7 SP3). ● Therefore, define the following settings for smoothing times, ramp times and controller. Parameter Setting Function p2200 1 Setting of the signal source for switching the technology controller on/off. p2253 r2224 Technology controller setpoint ● r755.
Commissioning Additional settings 6.6.3 6 Overview of parameters Open the Parameters menu Selection of the Parameters menu on BOP-2 and IOP-2-BT Table 12: Parameter selection Overview of parameters The table below contains only an excerpt from the parameter list. You can find a complete list of parameters in List Manual CU230P, SIOS Entry-ID: 109782303.
6 Commissioning Additional settings Parameter Factory settings Function p0756 [0] - AI 0 (0-4) 0: Unipolar voltage input (0 V...10 V) p0756 [1] - AI 1 (0-4) 1: Unipolar voltage input monitored (2 V... 10 V) p0756 [2] - AI 2 (2-3, 6-8) p0756 [3] - AI 3 (6-8) 2: Unipolar current input (0 mA…20 mA) 3: Unipolar current input monitored (4 mA…20 mA) 4: Bipolar voltage input (-10 V...
Commissioning Additional settings Parameter Factory settings Function p1210 0 Automatic restart: 6 0: Disables automatic restart 1: Acknowledges all faults without restarting 4: Restart after power failure, without additional startup attempts 6: Restart after fault with additional startup attempts 14: Restart after power failure after manual acknowledgement 16: Restart after fault after manual acknowledgement 26: Acknowledging all faults and restarting for an ON command Recommended setting: 26 Durin
6 Commissioning Additional settings Parameter Factory settings Function p8401 1.1.1970 Date of real-time clock: [0] = Day (1 ... 31) [1] = Month (1 ...
Commissioning Backing up data (memory card) 6 6.7 Backing up data (memory card) SD cards up to 2GB are supported. Siemens memory cards provide other functions. For more information on supported memory cards, see chapter "Memory cards" in the manual CU230P-2, SIOS Entry-ID: 109782866. NOTICE Risk of data loss If the memory card already contains the settings of another variable speed drive, the device adopts those settings. Data may be lost. ● Use an empty memory card.
Application examples 7 Factory settings 7 Application examples Basic commissioning (Carrying out basic commissioning [➙ 55]) is a prerequisite for the implementation of the application examples. During basic commissioning, the applications below can be parameterized directly via the macro parameter p0015. If the applications have to be set subsequently, the device must be set to commissioning state. Example: p0010 = 1 → p0015 = 101 → p0010 = 0 7.
Application examples Universal application Parameter Value Description p731 r52.2 Signal source for terminal DO 1 p756[0] 0 Unipolar voltage input (0...10 V) p840[0] r20047.0 ON / OFF (OFF1) p1000[0] 32 Speed setpoint selection p1001[0] 800 rpm Fixed speed setpoint 1 p1002[0] 1000 rpm Fixed speed setpoint 2 p1003[0] 1200 rpm Fixed speed setpoint 3 p1015[0] 1500 rpm Fixed speed setpoint 15 p1020[0] r722.3 Fixed speed setpoint selection bit 0 p1021[0] r722.
Application examples 7 Pump pressure control 7.3 Pump pressure control ● Macro 103 "Pump pressure control" ● Differential pressure regulated by integrated PID controller ● Flying restart and automatic restart activated ● Error message: Digital output 0 ● Status display: Digital output 2 When selecting this application using macro 103, the technological unit remains unchanged at [%]. If necessary, adapt the unit as described in the parameter list. Select the values depending on the used sensor.
Application examples Pressure controlled supply fan + ESM fixed speed 7 7.
Application examples 7 Cooling tower fan (LG-Ni1000) + hibernation 7.5 Cooling tower fan (LG-Ni1000) + hibernation ● Macro 107 "Cooling tower LG-Ni1000 sensor + hibernation" 9 5 ● Control of the cooling tower fan based on the temperature of the cooling water ● LG-Ni1000 temperature sensor on AI3 28 ● Hibernation 69 ● Flying restart and automatic restart activated ● ● Error message: Digital output 0 Status display: Digital output 2 ON / OFF P24V AO0+ 12 AO0- 13 Speed (0..
Application examples Cooling tower fan (active sensor) + hibernation 7 7.
Application examples 7 Stairwell pressurization (ESM) 7.7 Stairwell pressurization (ESM) ● Macro 104 "ESM stairwell pressurization" ● Central fire alarm system starts the fan ● Essential service mode (in the event of fire) with pressurization, e.g.
Application examples Fixed setpoints 7 7.8 Fixed setpoints ● Macro 111 "Fixed setpoints" ● Release and selection of 4 fixed speeds via digital inputs 0 to 4 ● Error message: Digital output 0 ● Status display: Digital output 2 ● If there are several inputs active simultaneously, the setpoints are added. Combined with three inputs, there are six different speed levels available. The drive starts when one of the inputs is in ON position. Parameter Value Description p840[0] r1025.
Application examples 7 CO2 sensor, 2 PID setpoints 7.9 CO2 sensor, 2 PID setpoints ● Macro 112 "CO2 sensor, 2 PID setpoints" ● ON/OFF and PID setpoint selection via DI0 or DI2 ● 9 ON / OFF Setpoint 1 External fault ON / OFF Setpoint 2 Set the fixed setpoint (50 % corresponding to the CO2 equivalent 1000 ppm) 5 6 7 ● External alarm at DI1. The fan is stopped.
Application examples Temperature-dependent pressure setpoint 7 7.10 Temperature-dependent pressure setpoint ● Macro 113 "Temperature-dependent pressure setpoint" ● Pressure control setpoint dependent on outside temperature and limited between 20% and 50% Pressure Setpoint [% ] 50 % 20 % O utside Tem perature [°C ] - 20°C + 5°C ● LG-Ni1000 temperature sensor on AI2 ● Pressure sensor 0...
7 Application examples Fan with belt monitoring function 7.
Application examples Pressure-controlled pump with cascade 7 7.12 Pressure-controlled pump with cascade Parameter Value Description p0730 r2379.0 Signal source for digital output 0: Control external motor 1 via DO 0 p0731 r2379.1 Signal source for digital output 1: Control external motor 2 via DO 1 p0732 r2379.2 Signal source for digital output 2: Control external motor 3 via DO 2 p756[0] 0 Unipolar voltage input (0...10 V) p0840 r722.
7 Application examples Fans in 87 Hz operation 7.13 Fans in 87 Hz operation Example for the following motor: Figure 27: Example motor for 87 Hz operation Carry out basic commissioning with 230V data ● IOP-2-BT/BOP-2: Select "87 Hz characteristic". ● Starter: Select connection type "Delta" and "87 Hz calculation". Parameter Value Description p0304 230 V Rated motor voltage p0305 0.73 A Rated motor current p0307 0.12 kW Rated motor output p0308 0.
Service, maintenance and fault rectification Safety guidelines for service, maintenance and fault rectification 8 8 Service, maintenance and fault rectification 8.1 Safety guidelines for service, maintenance and fault rectification WARNING Risk of injury as a result of improper service, maintenance and fault rectification! Failure to perform service, maintenance or fault rectification correctly can result in serious physical injury or property damage.
8 Service, maintenance and fault rectification Fault rectification 8.2.2 Fan maintenance The average service life of fans is 40 000 hours. In practice, the service life may differ from this value, in particular in dusty environments. The fan must be replaced in good time in order to ensure that the drive remains ready for operation.
Service, maintenance and fault rectification Fault rectification 8 The flashing frequencies of the LEDs have the following meaning: LED 8.3.
8 Service, maintenance and fault rectification Fault rectification Number Cause Solution A01910 Setpoint timeout: p2040 ≠ 0 ms and one of the following causes: 1. F01910 A01920 A03520 A05000 A05001 ● The bus connection is interrupted ● The MODBUS master is switched off ● Communications error (CRC, parity bit, logical error) PROFIBUS: Cyclic connection interrupt 2. 3. The cyclic connection to the PROFIBUS master is interrupted.
Service, maintenance and fault rectification Fault rectification Number Cause Solution A07910 Motor overtemperature 1. 2. 3. 4. A07920 Torque/speed too low F07923 Check the motor load. Check the ambient temperature and the motor ventilation. Check the KTY84 / Pt 1000 sensor. Check the overtemperatures of the thermal model (p0626 ... p0628). The torque deviates from the torque/speed envelope curve. 1. 2. A07921 8 Check the connection between the motor and load.
8 Service, maintenance and fault rectification Fault rectification Number Cause Solution F01044 Fault loading the data from the memory card Replace the memory card of the CU. F01105 Insufficient memory Reduce the number of data records. F01122 Frequency at the probe input too high Reduce the frequency of the pulses at the measuring input. F01205 Time slice overflow Contact Technical Support. F01250 CU hardware fault Replace the CU.
Service, maintenance and fault rectification Fault rectification 8 Number Cause Solution F07330 Search current measured too low 1. 2. F07426 Technology controller actual value limited The actual value for the technology controller which is interconnected via connector input p2264 has reached a limit. 1. 2. F07801 Motor overcurrent 3. 4. 5. 6. 7. 8. Regenerative power limit exceeded 1. 2. 3. 4. F07807 Short-circuit detected Adjust the limits to the signal level (p2267, p2268).
8 Service, maintenance and fault rectification Fault rectification Number Cause Solution A07929 No motor detected The magnitude of the current following enabling of the drive pulses is so small that no motor is detected. 1. 2. 3. 4. A07994 Motor data identification not The "Vector control" mode is set but motor data carried out identification has not yet been carried out. 1. 2. F30001 Check the motor cables, contactors and switches. Reduce the threshold value (p2179, e.g.
Service, maintenance and fault rectification Fault rectification Number Cause Solution F30022 Power Module: UCE monitoring 1. 2. Check the Power Module. Replace the Power Module, if necessary. F30027 Time monitoring for DC-link pre-charging 1. 2. Check the supply voltage at the input terminals. Check the line voltage setting (p0210). F30035 Overtemperature, intake air 1. 2. Overtemperature, inside 3. area Check whether the fan is running. Check the fan elements. Check the ambient temperature.
8 Service, maintenance and fault rectification Fault rectification 8.3.3.1 Tests without a power supply DANGER Danger due to electric current! If the terminals are not accessible externally, do not open the device because you will be exposed to a great risk and this will invalidate the warranty. ● In this case, contact your local Siemens branch office.
Service, maintenance and fault rectification Fault rectification 8 Static check on the drive The following checks are standard tests. These tests can be performed on most drives which are designed in accordance with the conventional principle "Rectifier – DC bus – IGBT bridge". The DC bus terminals of the PM230/G120P device are not generally used. However, the terminals are accessible on some models. Set the multimeter to "Diode" in order to measure the terminals.
8 Service, maintenance and fault rectification Fault rectification How to proceed if a fault is discovered The variable speed drive has failed one of these tests: Remove the Power Module (power unit) in order to replace or repair it. A short circuit is present at the input rectifiers or at components of the IGBT bridge: Check the state of fuses in the supply line, of contactors, disconnectors or of the motor itself.
Service, maintenance and fault rectification Fault rectification 8.3.3.2 8 Power test DANGER Danger due to electric current and moving parts during commissioning of equipment or plant! Components connected to the variable speed drive might move randomly while the drive is being commissioned. Movements of this kind can cause serious physical injury or death. ● Before commissioning the drive, make the system safe, for example by cordoning it off.
8 Service, maintenance and fault rectification Fault rectification 8.3.3.3 Function test Preliminary test Perform the preliminary tests set out in the table below without the motor connected. Only in this way can you be certain that any faults discovered are attributable to the variable speed drive rather than the connected motor. Check/Test Description MANUAL operation 1. 2. 3. 4. 5. OK Monitor the motor output terminals using a suitable multimeter which is also capable of measuring PWM voltages.
Service, maintenance and fault rectification Fault rectification 8 IOP diagnostics The following procedures are designed to test the wiring. They ensure that the correct signals reach the drive. If this reveals that the control wiring is correct, either the drive is defective or the configuration is incorrect. Check/Test Description IOP diagnostics – digital inputs 1. IOP diagnostics – digital outputs IOP diagnostics – analog inputs IOP diagnostics – analog outputs Siemens Smart Infrastructure 2. 1.
8 Service, maintenance and fault rectification Fault rectification IOP simulation Perform the following checks to test the inputs of the drive. These tests can detect wiring errors and any potential errors in the variable speed drive settings. Check/Test Description IOP I/O simulation 1. 2. OK Select the "Diagnostics / I/O simulation" menu. If the drive output responds to the simulation steps performed, this indicates that the drive is probably working properly but that the wiring is incorrect.
Technical data Functional data 9 9 Technical data 9.1 Functional data Electrical data Power (low overload LO) 0.75 to 90 kW Line voltage 380 to 480 V 3 AC ±10 % Line frequency 47 to 63 Hz Overload capability of frame sizes A – C (low overload LO) ● 1.5 x base-load current (150 %) for 3 s every 300 s ● 1.1 x base-load current (110%) for 57 s every 300 s Overload capability of frame sizes D – F (low overload LO) 1.
9 Technical data Functional data Permissible cable lengths IP55 Cable length 25 m 50 m 100 m Inverter, motor cable • Inverters with Category C2 filters • Shielded motor cable • Inverters with Category C1 filters • Shielded motor cable • Inverters with Category C2 filters • Shielded motor cable • Inverters with Category C1 filters • Shielded motor cable • Inverters with Category C2 filters • Unshielded motor cable • Inverters with Category C1 filters • UNshielded motor cable EMC
Technical data Functional data 9 Mechanical data Vibratory load ● Transport (in transport packaging) according to EN 60721-3-2 Class 2M3 ● Operation Test values according to EN 60068-2-6 Class 3M2 Shock stressing Siemens Smart Infrastructure ● Transport (in transport packaging) according to EN 60721-3-2 All devices and components Class 2M3 ● Operation Test values according to EN 60068-2-6 Frame sizes A to F Class 3M2 113 | 118 A5E36496664A_f 2021-10-11
9 Technical data Conformity 9.
Technical data Conformity 9 Directives and standards Description The following directives and standards are relevant for the converters: European Low Voltage Directive The converters fulfill the requirements stipulated in the Low-Voltage Directive 2014/35/EU, if they are covered by the application area of this directive. European Machinery Directive The converters fulfill the requirements stipulated in the Machinery Directive 2006/42/EC, if they are covered by the application area of this directive.
9 Technical data Conformity Eurasian conformity The converters comply with the requirements of the Russia/Belarus/Kazakhstan customs union (EAC). Australia and New Zealand (RCM formerly C-Tick) The converters showing the test symbols fulfill the EMC requirements for Australia and New Zealand. Immunity to voltage drop of semiconductor process equipment The converters comply with the requirements of standard SEMI F47-0706. China-RoHs The converters comply with the China-RoHs directive.
Appendix Commissioning report Conformity 10 10 Appendix Commissioning report Parameter Function Factory setting P0970 Restoring the factory setting - P1300 Control type 2 (U/f parabolic) P0100 Motor standard 0 (IEC motor) P0304 Rated motor voltage [V] P0305 Rated motor current [A] P0307 Motor power [kW] P0311 Rated motor speed [rpm] P1900 Motor data identification selection 0 P0015 Macro parameter 12 P1080 Minimum speed [rpm] 0 P1120 Ramp-up time [s] 10 P1121 Ramp-down tim
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a 6300 Zug Switzerland Tel. +41 58-724 24 24 www.siemens.com/buildingtechnologies Document ID: A5E36496664A_f Edition: 2021-10-11 © Siemens Switzerland Ltd, 2021 Technical specifications and availability subject to change without notice.