Operating Instructions

Application examples
Universal application
7
83 |
118
Siemens
A5E36496664A_f
Smart Infrastructure 2021-10-11
Parameter Value Description
p731 r52.2 Signal source for terminal DO 1
p756[0] 0 Unipolar voltage input (0...10 V)
p840[0] r20047.0 ON / OFF (OFF1)
p1000[0] 32 Speed setpoint selection
p1001[0] 800 rpm Fixed speed setpoint 1
p1002[0] 1000 rpm Fixed speed setpoint 2
p1003[0] 1200 rpm Fixed speed setpoint 3
p1015[0] 1500 rpm Fixed speed setpoint 15
p1020[0] r722.3 Fixed speed setpoint selection bit 0
p1021[0] r722.4 Fixed speed setpoint selection bit 1
p1022[0] r722.5 Fixed speed setpoint selection bit 2
p1071[0] r20220 Main setpoint scaling
p1113[0] 0 Setpoint inversion
p1200[0] 1 Flying restart always active (start in setpoint direction)
p1210 26 Acknowledging all faults and restarting for an ON command
p2103[0] 0 Acknowledge faults
p2106[0] r722.1 External fault
p3880 r722.2 ESM activation
p3881 1 ESM setpoint source: Fixed setpoint 15 (p1015)
p20046[0] r722.0 OR input I0
p20046[1] r1025.0 OR input I1
p20048 1 OR runtime group
p20218[0] 100% NSW input X0
p20218[1] 0 NSW input X1
p20219 r1025.0 NSW switch position I
p20221 5 NSW runtime group